HPXMLtoOpenStudio Measure¶
Introduction¶
The HPXMLtoOpenStudio measure requires a building description in an HPXML file format. HPXML is an open data standard for collecting and transferring home energy data. Using HPXML files reduces the complexity and effort for software developers to leverage the EnergyPlus simulation engine.
HPXML Inputs¶
HPXML is an flexible and extensible format, where nearly all elements in the schema are optional and custom elements can be included. Because of this, a stricter set of requirements for the HPXML file have been developed for purposes of running EnergyPlus simulations.
HPXML files submitted to OpenStudio-HPXML should undergo a two step validation process:
- Validation against the HPXML Schema
The HPXML XSD Schema can be found at
HPXMLtoOpenStudio/resources/HPXML.xsd
. It should be used by the software developer to validate their HPXML file prior to running the simulation. XSD Schemas are used to validate what elements/attributes/enumerations are available, data types for elements/attributes, the number/order of children elements, etc.OpenStudio-HPXML does not validate the HPXML file against the XSD Schema and assumes the file submitted is valid.
- Validation using Schematron
The Schematron document for the EnergyPlus use case can be found at
HPXMLtoOpenStudio/resources/EPvalidator.xml
. Schematron is a rule-based validation language, expressed in XML using XPath expressions, for validating the presence or absence of inputs in XML files. As opposed to an XSD Schema, a Schematron document validates constraints and requirements based on conditionals and other logical statements. For example, if an element is specified with a particular value, the applicable enumerations of another element may change.OpenStudio-HPXML automatically validates the HPXML file against the Schematron document and reports any validation errors, but software developers may find it beneficial to also integrate Schematron validation into their software.
Important
Usage of both validation approaches (XSD and Schematron) is recommended for developers actively working on creating HPXML files for EnergyPlus simulations:
- Validation against XSD for general correctness and usage of HPXML
- Validation against Schematron for understanding XML document requirements specific to running EnergyPlus
Input Defaults¶
An increasing number of elements in the HPXML file are being made optional with “smart” defaults. Default values, equations, and logic are described throughout this documentation.
Most defaults can also be seen by using the debug
argument/flag when running the workflow on an actual HPXML file.
This will create a new HPXML file (in.xml
in the run directory) where additional fields are populated for inspection.
For example, suppose a HPXML file has a window defined as follows:
<Window>
<SystemIdentifier id='Window'/>
<Area>108.0</Area>
<Azimuth>0</Azimuth>
<UFactor>0.33</UFactor>
<SHGC>0.45</SHGC>
<AttachedToWall idref='Wall'/>
</Window>
In the in.xml
file, the window would have additional elements like so:
<Window>
<SystemIdentifier id='Window'/>
<Area>108.0</Area>
<Azimuth>0</Azimuth>
<UFactor>0.33</UFactor>
<SHGC>0.45</SHGC>
<InteriorShading>
<SystemIdentifier id='WindowInteriorShading'/>
<SummerShadingCoefficient>0.7</SummerShadingCoefficient>
<WinterShadingCoefficient>0.85</WinterShadingCoefficient>
</InteriorShading>
<FractionOperable>0.67</FractionOperable>
<AttachedToWall idref='Wall'/>
</Window>
Warning
The OpenStudio-HPXML workflow generally treats missing HPXML elements differently than elements provided but without additional detail.
For example, if an HPXML file has no Refrigerator
element defined, it will be interpreted as a building that has no refrigerator and modeled this way.
On the other hand, if there is a Refrigerator
element defined but no elements within, it is interpreted as a building that has a refrigerator, but no information about the refrigerator is known.
In this case, its details (e.g., location, energy use) will be defaulted in the model.
HPXML Software Info¶
High-level simulation inputs are entered in HPXML’s /HPXML/SoftwareInfo
.
Current inputs include simulation controls and HVAC sizing controls.
HPXML Simulation Control¶
EnergyPlus simulation controls can be entered in extension/SimulationControl
.
The simulation timestep can be optionally provided as Timestep
, where the value is in minutes and must be a divisor of 60.
If not provided, the default value of 60 (i.e., 1 hour) is used.
The simulation run period can be optionally specified with BeginMonth
/BeginDayOfMonth
and/or EndMonth
/EndDayOfMonth
.
The BeginMonth
/BeginDayOfMonth
provided must occur before EndMonth
/EndDayOfMonth
provided (e.g., a run period from 10/1 to 3/31 is invalid).
If not provided, default values of January 1st and December 31st will be used.
Whether to apply daylight saving time can be optionally denoted with DaylightSaving/Enabled
.
If either DaylightSaving
or DaylightSaving/Enabled
is not provided, DaylightSaving/Enabled
will default to true.
If daylight saving is enabled, the daylight saving period can be optionally specified with DaylightSaving/BeginMonth
, DaylightSaving/BeginDayOfMonth
, DaylightSaving/EndMonth
, and DaylightSaving/EndDayOfMonth
.
If not specified, dates will be defined according to the EPW weather file header; if not available there, default values of March 12 and November 5 will be used.
HPXML HVAC Sizing Control¶
HVAC equipment sizing controls can be entered in extension/HVACSizingControl
.
An optional AllowIncreasedFixedCapacities
element can be provided to describe how HVAC equipment with fixed capacities are handled.
If false, the user-specified fixed capacity will be used.
If true, the maximum of the user-specified fixed capacity and the heating/cooling design load will be used to reduce potential for unmet loads.
If not provided, the default value of false is used.
An optional UseMaxLoadForHeatPumps
element can be provided to describe how autosized heat pumps are handled.
If true, heat pumps are sized based on the maximum of heating and cooling design loads.
If false, heat pumps are sized per ACCA Manual J/S based on cooling design loads with some oversizing allowances for heating design loads.
If not provided, the default value of true is used.
HPXML Building Details¶
The building description is entered in HPXML’s /HPXML/Building/BuildingDetails
.
HPXML Building Summary¶
This section describes elements specified in HPXML’s BuildingSummary
.
These elements include Site
, BuildingOccupancy
, and BuildingConstruction
.
HPXML Site¶
The Site
element is used to describe the terrain and local shelter conditions as well as the presence of neighbors.
The terrain surrounding the building can be optionally entered as Site/SiteType
; if not provided, it is assumed to be “suburban”.
The local shelter coefficient can be entered as Site/extension/ShelterCoefficient
.
The shelter coefficient is defined by the AIM-2 infiltration model to account for nearby buildings, trees and obstructions.
If not provided, the value of 0.5 will be assumed.
Shelter Coefficient | Description |
---|---|
1.0 | No obstructions or local shielding |
0.9 | Light local shielding with few obstructions within two building heights |
0.7 | Local shielding with many large obstructions within two building heights |
0.5 | Heavily shielded, many large obstructions within one building height |
0.3 | Complete shielding with large buildings immediately adjacent |
Shading due to neighboring buildings can be defined inside an extension/Neighbors
element.
Each Neighbors/NeighborBuilding
element is required to have an Azimuth
and Distance
from the house.
A Height
is also optionally allowed; if not provided, the neighboring building is assumed to have the same height as the house.
HPXML Building Occupancy¶
The BuildingOccupancy
element is used to describe the occupants.
The number of occupants can be optionally provided as NumberofResidents
; if not provided, it is assumed that the number of occupants equal the number of bedrooms.
Note
Most occupancy assumptions (e.g., plug loads, appliance usage, hot water usage, etc.) are based on the number of bedrooms. The number of residents is solely used to determine heat gains from the occupants themselves.
HPXML Building Construction¶
The BuildingConstruction
element is used to describe high-level building information.
Fields include:
ResidentialFacilityType
: “single-family detached”, “single-family attached”, “apartment unit”, or “manufactured home”NumberofConditionedFloors
NumberofConditionedFloorsAboveGrade
: Note that this should include a walkout basement if present.NumberofBedrooms
NumberofBathrooms
: Optional. If not provided, it is calculated as \(\frac{NumberofBedrooms}{2} + 0.5\) based on the Building America House Simulation Protocols.ConditionedFloorArea
ConditionedBuildingVolume
orAverageCeilingHeight
extension/HasFlueOrChimney
: Optional. Specifies whether there is a flue (associated with heating system or water heater) or chimney. if not provided, it is assumed to be true if any of the following conditions are met:- heating system is non-electric
Furnace
,Boiler
,WallFurnace
,FloorFurnace
,Stove
, orFixedHeater
and AFUE/Percent is less than 0.89 - heating system is non-electric
Fireplace
- water heater is non-electric with energy factor (or equivalent calculated from uniform energy factor) less than 0.63
- heating system is non-electric
HPXML Weather Station¶
The ClimateandRiskZones/WeatherStation
element specifies the EnergyPlus weather file (EPW) to be used in the simulation.
The weather file can be entered in one of two ways:
- Using
WeatherStation/WMO
, which must be one of the acceptable TMY3 WMO station numbers found in theweather/data.csv
file. The full set of U.S. TMY3 weather files can be downloaded here. - Using
WeatherStation/extension/EPWFilePath
.
HPXML Enclosure¶
This section describes elements specified in HPXML’s Enclosure
.
All surfaces that bound different space types in the building (i.e., not just thermal boundary surfaces) must be specified in the HPXML file. For example, an attached garage would generally be defined by walls adjacent to conditioned space, walls adjacent to outdoors, a slab, and a roof or ceiling. For software tools that do not collect sufficient inputs for every required surface, the software developers will need to make assumptions about these surfaces or collect additional input.
The space types used in the HPXML building description are:
Space Type | Description | Temperature | Building Type |
---|---|---|---|
living space | Above-grade conditioned floor area | EnergyPlus calculation | Any |
attic - vented | EnergyPlus calculation | Any | |
attic - unvented | EnergyPlus calculation | Any | |
basement - conditioned | Below-grade conditioned floor area | EnergyPlus calculation | Any |
basement - unconditioned | EnergyPlus calculation | Any | |
crawlspace - vented | EnergyPlus calculation | Any | |
crawlspace - unvented | EnergyPlus calculation | Any | |
garage | Single-family garage (not shared parking garage) | EnergyPlus calculation | Any |
other housing unit | E.g., conditioned adjacent unit or corridor | Same as conditioned space | Attached/Multifamily only |
other heated space | E.g., shared laundry/equipment space | Average of conditioned space and outside; minimum of 68F | Attached/Multifamily only |
other multifamily buffer space | E.g., enclosed unconditioned stairwell | Average of conditioned space and outside; minimum of 50F | Attached/Multifamily only |
other non-freezing space | E.g., shared parking garage ceiling | Floats with outside; minimum of 40F | Attached/Multifamily only |
Warning
It is the software tool’s responsibility to provide the appropriate building surfaces. While some error-checking is in place, it is not possible to know whether some surfaces are incorrectly missing.
Also note that wall and roof surfaces do not require an azimuth to be specified. Rather, only the windows/skylights themselves require an azimuth. Thus, software tools can choose to use a single wall (or roof) surface to represent multiple wall (or roof) surfaces for the entire building if all their other properties (construction type, interior/exterior adjacency, etc.) are identical.
HPXML Air Infiltration¶
Building air leakage is entered using Enclosure/AirInfiltration/AirInfiltrationMeasurement
.
Air leakage can be provided in one of three ways:
- nACH (natural air changes per hour): Use
BuildingAirLeakage/UnitofMeasure='ACHnatural'
. - ACH (air changes per hour at user-specified pressure): Use
BuildingAirLeakage/UnitofMeasure='ACH'
andHousePressure
. Pressure is typically 50 Pa. - CFM (cubic feet per minute at user-specified pressure): Use
BuildingAirLeakage/UnitofMeasure='CFM'
andHousePressure
. Pressure is typically 50 Pa.
In addition, the building’s volume associated with the air leakage measurement can be provided in HPXML’s AirInfiltrationMeasurement/InfiltrationVolume
.
If not provided, the infiltration volume is assumed to be equal to the conditioned building volume.
HPXML Attics/Foundations¶
The ventilation rate for vented attics (or vented crawlspaces) can be specified using an Attic
(or Foundation
) element.
First, define the AtticType
as Attic[Vented='true']
(or FoundationType
as Crawlspace[Vented='true']
).
Then specify the specific leakage area (SLA) using the VentilationRate[UnitofMeasure='SLA']/Value
element.
For vented attics, the natural air changes per hour (nACH) can instead be specified using UnitofMeasure='ACHnatural'
.
If the ventilation rate is not provided, default values of SLA=1/300 for vented attics and SLA=1/150 for vented crawlspaces will be used based on ANSI/RESNET/ICC 301-2019.
HPXML Roofs¶
Pitched or flat roof surfaces that are exposed to ambient conditions should be specified as an Enclosure/Roofs/Roof
.
For a multifamily building where the dwelling unit has another dwelling unit above it, the surface between the two dwelling units should be considered a FrameFloor
and not a Roof
.
Roofs are defined by their Area
, Pitch
, Insulation/AssemblyEffectiveRValue
, SolarAbsorptance
, and Emittance
.
Roofs must have either RoofColor
and/or SolarAbsorptance
defined.
If RoofColor
or SolarAbsorptance
is not provided, it is defaulted based on the mapping below:
RoofColor | RoofMaterial | SolarAbsorptance |
---|---|---|
dark | asphalt or fiberglass shingles, wood shingles or shakes | 0.92 |
medium dark | asphalt or fiberglass shingles, wood shingles or shakes | 0.89 |
medium | asphalt or fiberglass shingles, wood shingles or shakes | 0.85 |
light | asphalt or fiberglass shingles, wood shingles or shakes | 0.75 |
reflective | asphalt or fiberglass shingles, wood shingles or shakes | 0.50 |
dark | slate or tile shingles, metal surfacing | 0.90 |
medium dark | slate or tile shingles, metal surfacing | 0.83 |
medium | slate or tile shingles, metal surfacing | 0.75 |
light | slate or tile shingles, metal surfacing | 0.60 |
reflective | slate or tile shingles, metal surfacing | 0.30 |
Roofs can also have optional elements provided for RadiantBarrier and ``RoofType
.
If RadiantBarrier
is not provided, it is defaulted to not present; if it is provided, RadiantBarrierGrade
must also be provided.
If RoofType
is not provided, it is defaulted to “asphalt or fiberglass shingles”.
HPXML Rim Joists¶
Rim joists, the perimeter of floor joists typically found between stories of a building or on top of a foundation wall, are specified as an Enclosure/RimJoists/RimJoist
.
The InteriorAdjacentTo
element should typically be “living space” for rim joists between stories of a building and “basement - conditioned”, “basement - unconditioned”, “crawlspace - vented”, or “crawlspace - unvented” for rim joists on top of a foundation wall.
Rim joists are defined by their Area
and Insulation/AssemblyEffectiveRValue
.
Rim joists must have either Color
and/or SolarAbsorptance
defined.
If Color
or SolarAbsorptance
is not provided, it is defaulted based on the mapping below:
Color | SolarAbsorptance |
---|---|
dark | 0.95 |
medium dark | 0.85 |
medium | 0.70 |
light | 0.50 |
reflective | 0.30 |
Rim joists can have an optional element provided for Siding
; if not provided, it defaults to “wood siding”.
HPXML Walls¶
Any wall that has no contact with the ground and bounds a space type should be specified as an Enclosure/Walls/Wall
.
Interior walls (for example, walls solely within the conditioned space of the building) are not required.
Walls are defined by their Area
and Insulation/AssemblyEffectiveRValue
.
The choice of WallType
has a secondary effect on heat transfer in that it informs the assumption of wall thermal mass.
Walls must have either Color
and/or SolarAbsorptance
defined.
If Color
or SolarAbsorptance
is not provided, it is defaulted based on the mapping below:
Color | SolarAbsorptance |
---|---|
dark | 0.95 |
medium dark | 0.85 |
medium | 0.70 |
light | 0.50 |
reflective | 0.30 |
Walls can have an optional element provided for Siding
; if not provided, it defaults to “wood siding”.
HPXML Foundation Walls¶
Any wall that is in contact with the ground should be specified as an Enclosure/FoundationWalls/FoundationWall
.
Other walls (e.g., wood framed walls) that are connected to a below-grade space but have no contact with the ground should be specified as Walls
and not FoundationWalls
.
Exterior foundation walls (i.e., those that fall along the perimeter of the building’s footprint) should use “ground” for ExteriorAdjacentTo
and the appropriate space type (e.g., “basement - unconditioned”) for InteriorAdjacentTo
.
Interior foundation walls should be specified with two appropriate space types (e.g., “crawlspace - vented” and “garage”, or “basement - unconditioned” and “crawlspace - unvented”) for InteriorAdjacentTo
and ExteriorAdjacentTo
.
Interior foundation walls should never use “ground” for ExteriorAdjacentTo
even if the foundation wall has some contact with the ground due to the difference in below-grade depths of the two adjacent space types.
Foundations must include a Height
as well as a DepthBelowGrade
.
For exterior foundation walls, the depth below grade is relative to the ground plane.
For interior foundation walls, the depth below grade should not be thought of as relative to the ground plane, but rather as the depth of foundation wall in contact with the ground.
For example, an interior foundation wall between an 8 ft conditioned basement and a 3 ft crawlspace has a height of 8 ft and a depth below grade of 5 ft.
Alternatively, an interior foundation wall between an 8 ft conditioned basement and an 8 ft unconditioned basement has a height of 8 ft and a depth below grade of 0 ft.
Foundation wall insulation can be described in two ways:
Option 1. Both interior and exterior continuous insulation layers with NominalRValue
, extension/DistanceToTopOfInsulation
, and extension/DistanceToBottomOfInsulation
.
Insulation layers are particularly useful for describing foundation wall insulation that doesn’t span the entire height (e.g., 4 ft of insulation for an 8 ft conditioned basement).
If there is not insulation on the interior and/or exterior of the foundation wall, the continuous insulation layer must still be provided – with the nominal R-value, etc., set to zero.
When insulation is specified with option 1, it is modeled with a concrete wall (whose Thickness
is provided) as well as air film resistances as appropriate.
Option 2. An AssemblyEffectiveRValue
.
The assembly effective R-value should include the concrete wall and an interior air film resistance.
The exterior air film resistance (for any above-grade exposure) or any soil thermal resistance should not be included.
HPXML Frame Floors¶
Any horizontal floor/ceiling surface that is not in contact with the ground (Slab) nor adjacent to ambient conditions above (Roof) should be specified as an Enclosure/FrameFloors/FrameFloor
.
Frame floors in an attached/multifamily building that are adjacent to “other housing unit”, “other heated space”, “other multifamily buffer space”, or “other non-freezing space” must have the extension/OtherSpaceAboveOrBelow
property set to signify whether the other space is “above” or “below”.
Frame floors are primarily defined by their Insulation/AssemblyEffectiveRValue
.
HPXML Slabs¶
Any space type that borders the ground should include an Enclosure/Slabs/Slab
surface with the appropriate InteriorAdjacentTo
.
This includes basements, crawlspaces (even when there are dirt floors – use zero for the Thickness
), garages, and slab-on-grade foundations.
A primary input for a slab is its ExposedPerimeter
.
The exposed perimeter should include any slab length that falls along the perimeter of the building’s footprint (i.e., is exposed to ambient conditions).
So, a basement slab edge adjacent to a garage or crawlspace, for example, should not be included.
Vertical insulation adjacent to the slab can be described by a PerimeterInsulation/Layer/NominalRValue
and a PerimeterInsulationDepth
.
Horizontal insulation under the slab can be described by a UnderSlabInsulation/Layer/NominalRValue
.
The insulation can either have a fixed width (UnderSlabInsulationWidth
) or can span the entire slab (UnderSlabInsulationSpansEntireSlab
).
For foundation types without walls, the DepthBelowGrade
element must be provided.
For foundation types with walls, the DepthBelowGrade
element is not used; instead the slab’s position relative to grade is determined by the FoundationWall/DepthBelowGrade
values.
HPXML Windows¶
Any window or glass door area should be specified as an Enclosure/Windows/Window
.
Windows are defined by full-assembly NFRC UFactor
and SHGC
, as well as Area
.
Windows must reference a HPXML Enclosures/Walls/Wall
element via the AttachedToWall
.
Windows must also have an Azimuth
specified, even if the attached wall does not.
In addition, the summer/winter interior shading coefficients can be optionally entered as InteriorShading/SummerShadingCoefficient
and InteriorShading/WinterShadingCoefficient
.
The summer interior shading coefficient must be less than or equal to the winter interior shading coefficient.
Note that a value of 0.7 indicates a 30% reduction in solar gains (i.e., 30% shading).
If not provided, default values of 0.70 for summer and 0.85 for winter will be used based on ANSI/RESNET/ICC 301-2019.
Overhangs (e.g., a roof eave) can optionally be defined for a window by specifying a Window/Overhangs
element.
Overhangs are defined by the vertical distance between the overhang and the top of the window (DistanceToTopOfWindow
), and the vertical distance between the overhang and the bottom of the window (DistanceToBottomOfWindow
).
The difference between these two values equals the height of the window.
Finally, windows can be optionally described with FractionOperable
.
The input should solely reflect whether the windows are operable (can be opened), not how they are used by the occupants.
If a Window
represents a single window, the value should be 0 or 1.
If a Window
represents multiple windows (e.g., 4), the value should be between 0 and 1 (e.g., 0, 0.25, 0.5, 0.75, or 1).
If not provided, it is assumed that 67% of the windows are operable.
The total open window area for natural ventilation is thus calculated using A) the fraction of windows that are operable, B) the assumption that 50% of the area of operable windows can be open, and C) the assumption that 20% of that openable area is actually opened by occupants whenever outdoor conditions are favorable for cooling.
HPXML Skylights¶
Any skylight should be specified as an Enclosure/Skylights/Skylight
.
Skylights are defined by full-assembly NFRC UFactor
and SHGC
, as well as Area
.
Skylights must reference a HPXML Enclosures/Roofs/Roof
element via the AttachedToRoof
.
Skylights must also have an Azimuth
specified, even if the attached roof does not.
In addition, the summer/winter interior shading coefficients can be optionally entered as InteriorShading/SummerShadingCoefficient
and InteriorShading/WinterShadingCoefficient
.
The summer interior shading coefficient must be less than or equal to the winter interior shading coefficient.
Note that a value of 0.7 indicates a 30% reduction in solar gains (i.e., 30% shading).
If not provided, default values of 1.0 for summer and 1.0 for winter will be used.
HPXML Doors¶
Any opaque doors should be specified as an Enclosure/Doors/Door
.
Doors are defined by RValue
and Area
.
Doors must reference a HPXML Enclosures/Walls/Wall
element via the AttachedToWall
.
Doors must also have an Azimuth
specified, even if the attached wall does not.
HPXML Systems¶
This section describes elements specified in HPXML’s Systems
.
If any HVAC systems are entered that provide heating (or cooling), the sum of all their FractionHeatLoadServed
(or FractionCoolLoadServed
) values must be less than or equal to 1.
For example, a room air conditioner might be specified with FractionCoolLoadServed
equal to 0.3 if it serves 30% of the home’s conditioned floor area.
If any water heating systems are entered, the sum of all their FractionDHWLoadServed
values must be equal to 1.
HPXML Heating Systems¶
Each heating system (other than heat pumps) should be entered as a Systems/HVAC/HVACPlant/HeatingSystem
.
Inputs including HeatingSystemType
, and FractionHeatLoadServed
must be provided.
Depending on the type of heating system specified, additional elements are used:
HeatingSystemType | IsSharedSystem | DistributionSystem | HeatingSystemFuel | AnnualHeatingEfficiency | HeatingCapacity |
---|---|---|---|---|---|
ElectricResistance | electricity | Percent | (optional) | ||
Furnace | AirDistribution or DSE | <any> | AFUE | (optional) | |
WallFurnace | <any> | AFUE | (optional) | ||
FloorFurnace | <any> | AFUE | (optional) | ||
Boiler | false | HydronicDistribution or DSE | <any> | AFUE | (optional) |
Boiler | true | HydronicDistribution or HydronicAndAirDistribution | <any> | AFUE | |
Stove | <any> | Percent | (optional) | ||
PortableHeater | <any> | Percent | (optional) | ||
Fireplace | <any> | Percent | (optional) |
For all non-shared systems, HeatingCapacity
may be provided; if not, the system will be auto-sized via ACCA Manual J/S.
For all systems, the ElectricAuxiliaryEnergy
element may be provided if available.
For shared boilers (i.e., serving multiple dwelling units), the electric auxiliary energy can alternatively be calculated as follows per ANSI/RESNET/ICC 301-2019:
\(EAE = (\frac{SP}{N_{dweq}} + aux_{in}) \cdot HLH\)where,\(SP\) = Shared pump power [W], provided asextension/SharedLoopWatts
\(N_{dweq}\) = Number of units served by the shared system, provided asNumberofUnitsServed
\(aux_{in}\) = In-unit fan coil power [W], provided asextension/FanCoilWatts
\(HLH\) = Annual heating load hours
If electric auxiliary energy is not provided (nor calculated for shared boilers), it is defaulted per ANSI/RESNET/ICC 301-2019 as follows:
System Type | Electric Auxiliary Energy |
---|---|
Oil boiler | 330 |
Gas boiler (in-unit) | 170 |
Gas boiler (shared, w/ baseboard) | 220 |
Gas boiler (shared, w/ water loop heat pump) | 265 |
Gas boiler (shared, w/ fan coil) | 438 |
Oil furnace | 439 + 5.5 * Capacity (kBtu/h) |
Gas furnace | 149 + 10.3 * Capacity (kBtu/h) |
Other | 0 |
For shared boilers connected to a water loop heat pump, the heat pump’s heating COP must be provided as extension/WaterLoopHeatPump/AnnualHeatingEfficiency[Units="COP"]/Value
.
HPXML Cooling Systems¶
Each cooling system (other than heat pumps) should be entered as a Systems/HVAC/HVACPlant/CoolingSystem
.
Inputs including CoolingSystemType
and FractionCoolLoadServed
must be provided.
Depending on the type of cooling system specified, additional elements are used:
CoolingSystemType | IsSharedSystem | DistributionSystem | CoolingSystemFuel | AnnualCoolingEfficiency | SensibleHeatFraction | CoolingCapacity |
---|---|---|---|---|---|---|
central air conditioner | AirDistribution or DSE | electricity | SEER | (optional) | (optional) | |
room air conditioner | electricity | EER | (optional) | (optional) | ||
evaporative cooler | AirDistribution or DSE (optional) | electricity | ||||
mini-split | AirDistribution or DSE (optional) | electricity | SEER | (optional) | (optional) | |
chiller | true | HydronicDistribution or HydronicAndAirDistribution | electricity | kW/ton | (required) | |
cooling tower | true | HydronicAndAirDistribution | electricity |
Central air conditioners can also have the CompressorType
specified; if not provided, it is assumed as follows:
- “single stage”: SEER <= 15
- “two stage”: 15 < SEER <= 21
- “variable speed”: SEER > 21
For all non-shared systems other than evaporative coolers, CoolingCapacity
may be provided; if not, the system will be auto-sized via ACCA Manual J/S.
Shared chillers (i.e., serving multiple dwelling units) are modeled with a SEER equivalent using the following equation from ANSI/RESNET/ICC 301-2019:
\(SEER_{eq} = \frac{(Cap - (aux \cdot 3.41)) - (aux_{dweq} \cdot 3.41 \cdot N_{dweq})}{(Input \cdot aux) + (aux_{dweq} \cdot N_{dweq})}\)where,\(Cap\) = Chiller system output [Btu/hour], provided asCoolingCapacity
\(aux\) = Total of the pumping and fan power serving the system [W], provided asextension/SharedLoopWatts
\(aux_{dweq}\) = Total of the in-unit cooling equipment power serving the unit; for example, includes all power to run a Water Loop Heat Pump within the unit, not just air handler power [W], provided asextension/FanCoilWatts
for fan coils, or calculated asextension/WaterLoopHeatPump/CoolingCapacity
divided byextension/WaterLoopHeatPump/AnnualCoolingEfficiency[Units="EER"]/Value
for cooling towers, or zero for baseboard/radiators\(Input\) = Chiller system power [W], calculated usingAnnualCoolingEfficiency[Units="kW/ton"]/Value
\(N_{dweq}\) = Number of units served by the shared system, provided asNumberofUnitsServed
Shared cooling towers with water loop heat pumps are modeled with a SEER equivalent using the following equation from ANSI/RESNET/ICC 301-2019:
\(SEER_{eq} = \frac{WLHP_{cap} - \frac{aux \cdot 3.41}{N_{dweq}}}{Input + \frac{aux}{N_{dweq}}}\)where,\(WLHP_{cap}\) = WLHP cooling capacity [Btu/hr], provided asextension/WaterLoopHeatPump/CoolingCapacity
\(aux\) = Total of the pumping and fan power serving the system [W], provided asextension/SharedLoopWatts
\(N_{dweq}\) = Number of units served by the shared system, provided asNumberofUnitsServed
\(Input\) = WLHP system power [W], calculated asextension/WaterLoopHeatPump/CoolingCapacity
divided byextension/WaterLoopHeatPump/AnnualCoolingEfficiency[Units="EER"]/Value
HPXML Heat Pumps¶
Each heat pump should be entered as a Systems/HVAC/HVACPlant/HeatPump
.
Inputs including HeatPumpType
, FractionHeatLoadServed
, and FractionCoolLoadServed
must be provided.
Note that heat pumps are allowed to provide only heating (FractionCoolLoadServed
= 0) or cooling (FractionHeatLoadServed
= 0) if appropriate.
HeatingCapacity
and CoolingCapacity
may be provided; if not, the system will be auto-sized via ACCA Manual J/S.
Depending on the type of heat pump specified, additional elements are used:
HeatPumpType | IsSharedSystem | DistributionSystem | HeatPumpFuel | AnnualCoolingEfficiency | AnnualHeatingEfficiency | CoolingSensibleHeatFraction | HeatingCapacity17F |
---|---|---|---|---|---|---|---|
air-to-air | AirDistribution or DSE | electricity | SEER | HSPF | (optional) | (optional) | |
mini-split | AirDistribution or DSE (optional) | electricity | SEER | HSPF | (optional) | (optional) | |
ground-to-air | false | AirDistribution or DSE | electricity | EER | COP | (optional) | |
ground-to-air | true | AirDistribution or DSE | electricity | EER | COP | (optional) |
Ground-to-air heat pumps also have a few other inputs:
extension/PumpPowerWattsPerTon
: Optional. Ground loop circulator pump power during operation of the heat pump in Watts/ton of cooling capacity. Defaults to 30 Watts per ton of cooling capacity per ANSI/RESNET/ICC 301-2019 for a closed loop system.extension/FanPowerWattsPerCFM
: Optional. Blower fan power in Watts/cfm. Defaults to 0.5 W/cfm.
Air-to-air heat pumps can also have the CompressorType
specified; if not provided, it is assumed as follows:
- “single stage”: SEER <= 15
- “two stage”: 15 < SEER <= 21
- “variable speed”: SEER > 21
If the heat pump has backup heating, it can be specified with BackupSystemFuel
, BackupAnnualHeatingEfficiency
, and (optionally) BackupHeatingCapacity
.
If the heat pump has a switchover temperature (e.g., dual-fuel heat pump) where the heat pump stops operating and the backup heating system starts running, it can be specified with BackupHeatingSwitchoverTemperature
.
If the BackupHeatingSwitchoverTemperature
is not provided, the backup heating system will operate as needed when the heat pump has insufficient capacity.
For multiple ground source heat pumps on a shared hydronic circulation loop (IsSharedSystem="true"
), the loop’s annual electric consumption is calculated using the following equation from ANSI/RESNET/ICC 301-2019:
\(Eae = \frac{SP}{N_{dweq}} \cdot 8.760\)where,\(SP\) = Shared pump power [W], provided asextension/SharedLoopWatts
\(N_{dweq}\) = Number of units served by the shared system, provided asNumberofUnitsServed
HPXML HVAC Control¶
A Systems/HVAC/HVACControl
must be provided if any HVAC systems are specified.
The heating setpoint (SetpointTempHeatingSeason
) and cooling setpoint (SetpointTempCoolingSeason
) are required elements.
If there is a heating setback, it is defined with:
SetbackTempHeatingSeason
: Temperature during heating setbackextension/SetbackStartHourHeating
: The start hour of the heating setback where 0=midnight and 12=noonTotalSetbackHoursperWeekHeating
: The number of hours of heating setback per week
If there is a cooling setup, it is defined with:
SetupTempCoolingSeason
: Temperature during cooling setupextension/SetupStartHourCooling
: The start hour of the cooling setup where 0=midnight and 12=noonTotalSetupHoursperWeekCooling
: The number of hours of cooling setup per week
Finally, if there are sufficient ceiling fans present that result in a reduced cooling setpoint, this offset can be specified with extension/CeilingFanSetpointTempCoolingSeasonOffset
.
HPXML HVAC Distribution¶
Each separate HVAC distribution system should be specified as a Systems/HVAC/HVACDistribution
.
The four types of HVAC distribution systems allowed are AirDistribution
, HydronicDistribution
, HydronicAndAirDistribution
, and DSE
.
There should be at most one heating system and one cooling system attached to a distribution system.
See the sections on Heating Systems, Cooling Systems, and Heat Pumps for information on which DistributionSystemType
is allowed for which HVAC system.
Also note that some HVAC systems (e.g., room air conditioners) are not allowed to be attached to a distribution system.
Air Distribution¶
AirDistribution
systems are defined by:
ConditionedFloorAreaServed
- Optional
NumberofReturnRegisters
. If not provided, one return register per conditioned floor will be assumed. - Optional supply leakage to the outside in CFM25 or percent of airflow (
DuctLeakageMeasurement[DuctType='supply']/DuctLeakage/Value
) - Optional return leakage to the outside in CFM25 or percent of airflow (
DuctLeakageMeasurement[DuctType='return']/DuctLeakage/Value
) - Optional supply ducts (
Ducts[DuctType='supply']
) - Optional return ducts (
Ducts[DuctType='return']
)
For each duct, DuctInsulationRValue
must be provided.
DuctLocation
and DuctSurfaceArea
can be optionally provided.
The provided DuctLocation
can be one of the following:
Location | Description | Temperature | Building Type | Default Priority |
---|---|---|---|---|
living space | Above-grade conditioned floor area | EnergyPlus calculation | Any | 8 |
basement - conditioned | Below-grade conditioned floor area | EnergyPlus calculation | Any | 1 |
basement - unconditioned | EnergyPlus calculation | Any | 2 | |
crawlspace - unvented | EnergyPlus calculation | Any | 4 | |
crawlspace - vented | EnergyPlus calculation | Any | 3 | |
attic - unvented | EnergyPlus calculation | Any | 6 | |
attic - vented | EnergyPlus calculation | Any | 5 | |
garage | Single-family garage (not shared parking garage) | EnergyPlus calculation | Any | 7 |
outside | Outside | Any | ||
exterior wall | Average of conditioned space and outside | Any | ||
under slab | Ground | Any | ||
roof deck | Outside | Any | ||
other housing unit | E.g., conditioned adjacent unit or corridor | Same as conditioned space | Attached/Multifamily only | |
other heated space | E.g., shared laundry/equipment space | Average of conditioned space and outside; minimum of 68F | Attached/Multifamily only | |
other multifamily buffer space | E.g., enclosed unconditioned stairwell | Average of conditioned space and outside; minimum of 50F | Attached/Multifamily only | |
other non-freezing space | E.g., shared parking garage ceiling | Floats with outside; minimum of 40F | Attached/Multifamily only |
If DuctLocation
is not provided, the primary duct location will be chosen based on the presence of spaces and the “Default Priority” indicated above.
For a 2+ story home, secondary ducts will also be located in the living space.
If DuctSurfaceArea
is not provided, the total duct area will be calculated based on ANSI/ASHRAE Standard 152-2004:
Element Name | Default Value |
---|---|
DuctSurfaceArea (primary supply ducts) | \(0.27 \cdot F_{out} \cdot CFA_{ServedByAirDistribution}\) |
DuctSurfaceArea (secondary supply ducts) | \(0.27 \cdot (1 - F_{out}) \cdot CFA_{ServedByAirDistribution}\) |
DuctSurfaceArea (primary return ducts) | \(b_r \cdot F_{out} \cdot CFA_{ServedByAirDistribution}\) |
DuctSurfaceArea (secondary return ducts) | \(b_r \cdot (1 - F_{out}) \cdot CFA_{ServedByAirDistribution}\) |
where Fout is 1.0 for 1-story homes and 0.75 for 2+ story homes and br is 0.05 * NumberofReturnRegisters
with a maximum value of 0.25.
Hydronic Distribution¶
HydronicDistribution
systems are defined by:
HydronicDistributionType
: “radiator” or “baseboard” or “radiant floor” or “radiant ceiling”
Hydronic And Air Distribution¶
HydronicAndAirDistribution
systems are defined by:
HydronicAndAirDistributionType
: “fan coil” or “water loop heat pump”
as well as all of the elements described above for an AirDistribution
system.
Distribution System Efficiency¶
DSE
systems are defined by a AnnualHeatingDistributionSystemEfficiency
and AnnualCoolingDistributionSystemEfficiency
elements.
Warning
Specifying a DSE for the HVAC distribution system is reflected in the SimulationOutputReport reporting measure outputs, but is not reflected in the raw EnergyPlus simulation outputs.
HPXML Mechanical Ventilation¶
This section describes elements specified in HPXML’s Systems/MechanicalVentilation
.
Systems/MechanicalVentilation/VentilationFans/VentilationFan
elements can be used to specify whole home ventilation, local ventilation, and/or cooling load reduction.
Whole Home Ventilation¶
Mechanical ventilation systems that provide whole home ventilation may each be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with UsedForWholeBuildingVentilation='true'
.
Inputs including FanType
and HoursInOperation
must be provided.
Depending on the type of mechanical ventilation specified, additional elements are required:
FanType | SensibleRecoveryEfficiency | TotalRecoveryEfficiency | AttachedToHVACDistributionSystem |
---|---|---|---|
energy recovery ventilator | required | required | |
heat recovery ventilator | required | ||
exhaust only | |||
supply only | |||
balanced | |||
central fan integrated supply (CFIS) | required |
Note that AdjustedSensibleRecoveryEfficiency
and AdjustedTotalRecoveryEfficiency
can be provided instead of SensibleRecoveryEfficiency
and TotalRecoveryEfficiency
.
The ventilation system may be optionally described as a shared system (i.e., serving multiple dwelling units) using IsSharedSystem
.
If not provided, it is assumed to be false.
If the ventilation system is not shared, the following inputs are available:
TestedFlowRate
orRatedFlowRate
: The airflow rate. For a CFIS system, the flow rate should equal the amount of outdoor air provided to the distribution system.FanPower
: The fan power for the highest airflow setting.
If the ventilation system is shared, the following inputs are available:
TestedFlowRate
orRatedFlowRate
: The airflow rate of the entire system.FanPower
: The fan power for the entire system at highest airflow setting.FractionRecirculation
: Fraction of the total supply air that is recirculated, with the remainder assumed to be outdoor air. The value must be 0 for exhaust only systems.extension/InUnitFlowRate
: The flow rate delivered to the dwelling unit.extension/PreHeating
: Optional. Element to specify if the supply air is preconditioned by heating equipment. It is not allowed for exhaust only systems. If provided, there are additional child elements required:Fuel
: Fuel type of the preconditioning heating equipment.AnnualHeatingEfficiency[Units="COP"]/Value
: Efficiency of the preconditioning heating equipment.FractionVentilationHeatLoadServed
: Fraction of heating load introduced by the shared ventilation system that is met by the preconditioning heating equipment.
extension/PreCooling
: Optional. Element to specify if the supply air is preconditioned by cooling equipment. It is not allowed for exhaust only systems. If provided, there are additional child elements required:Fuel
: Fuel type of the preconditioning cooling equipment.AnnualCoolingEfficiency[Units="COP"]/Value
: Efficiency of the preconditioning cooling equipment.FractionVentilationCoolLoadServed
: Fraction of cooling load introduced by the shared ventilation system that is met by the preconditioning cooling equipment.
Local Ventilation¶
Kitchen range fans that provide local ventilation may each be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with FanLocation='kitchen'
and UsedForLocalVentilation='true'
.
Additional fields may be provided per the table below. If not provided, default values will be assumed based on the Building America House Simulation Protocols.
Element Name | Default Value |
---|---|
Quantity [#] | 1 |
RatedFlowRate [cfm] | 100 |
HoursInOperation [hrs/day] | 1 |
FanPower [W] | 0.3 * RatedFlowRate |
extension/StartHour [0-23] | 18 |
Bathroom fans that provide local ventilation may each be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with FanLocation='bath'
and UsedForLocalVentilation='true'
.
Additional fields may be provided per the table below. If not provided, default values will be assumed based on the Building America House Simulation Protocols.
Element Name | Default Value |
---|---|
Quantity [#] | NumberofBathrooms |
RatedFlowRate [cfm] | 50 |
HoursInOperation [hrs/day] | 1 |
FanPower [W] | 0.3 * RatedFlowRate |
extension/StartHour [0-23] | 7 |
Cooling Load Reduction¶
Whole house fans that provide cooling load reduction may each be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with UsedForSeasonalCoolingLoadReduction='true'
.
Required elements include RatedFlowRate
and FanPower
.
The whole house fan is assumed to operate during hours of favorable outdoor conditions and will take priority over operable windows (natural ventilation).
HPXML Water Heating Systems¶
Each water heater should be entered as a Systems/WaterHeating/WaterHeatingSystem
.
Inputs including WaterHeaterType
and FractionDHWLoadServed
must be provided.
Warning
FractionDHWLoadServed
represents only the fraction of the hot water load associated with the hot water fixtures. Additional hot water load from the clothes washer/dishwasher will be automatically assigned to the appropriate water heater(s).
Depending on the type of water heater specified, additional elements are required/available:
WaterHeaterType | UniformEnergyFactor or EnergyFactor | FuelType | TankVolume | HeatingCapacity | RecoveryEfficiency | PerformanceAdjustment | UsesDesuperheater | WaterHeaterInsulation/Jacket/JacketRValue | RelatedHVACSystem |
---|---|---|---|---|---|---|---|---|---|
storage water heater | required | <any> | (optional) | (optional) | (optional) | (optional) | (optional) | required if uses desuperheater | |
instantaneous water heater | required | <any> | (optional) | (optional) | required if uses desuperheater | ||||
heat pump water heater | required | electricity | required | (optional) | (optional) | required if uses desuperheater | |||
space-heating boiler with storage tank | required | (optional) | required | ||||||
space-heating boiler with tankless coil | required |
For storage water heaters, the tank volume in gallons, heating capacity in Btuh, and recovery efficiency can be optionally provided. If not provided, default values for the tank volume and heating capacity will be assumed based on Table 8 in the 2014 Building America House Simulation Protocols and a default recovery efficiency shown in the table below will be assumed based on regression analysis of AHRI certified water heaters.
EnergyFactor | RecoveryEfficiency (default) |
---|---|
>= 0.75 | 0.778114 * EF + 0.276679 |
< 0.75 | 0.252117 * EF + 0.607997 |
For tankless water heaters, a performance adjustment due to cycling inefficiencies can be provided. If not provided, a default value of 0.92 (92%) will apply to the Energy Factor.
For combi boiler systems, the RelatedHVACSystem
must point to a HeatingSystem
of type “Boiler”.
For combi boiler systems with a storage tank, the storage tank losses (deg-F/hr) can be entered as StandbyLoss
; if not provided, a default value based on the AHRI Directory of Certified Product Performance will be calculated.
For water heaters that are connected to a desuperheater, the RelatedHVACSystem
must either point to a HeatPump
or a CoolingSystem
.
The water heater Location
can be optionally entered as one of the following:
Location | Description | Temperature | Building Type |
---|---|---|---|
living space | Above-grade conditioned floor area | EnergyPlus calculation | Any |
basement - conditioned | Below-grade conditioned floor area | EnergyPlus calculation | Any |
basement - unconditioned | EnergyPlus calculation | Any | |
attic - unvented | EnergyPlus calculation | Any | |
attic - vented | EnergyPlus calculation | Any | |
garage | Single-family garage (not shared parking garage) | EnergyPlus calculation | Any |
crawlspace - unvented | EnergyPlus calculation | Any | |
crawlspace - vented | EnergyPlus calculation | Any | |
other exterior | Outside | EnergyPlus calculation | Any |
other housing unit | E.g., conditioned adjacent unit or corridor | Same as conditioned space | Attached/Multifamily only |
other heated space | E.g., shared laundry/equipment space | Average of conditioned space and outside; minimum of 68F | Attached/Multifamily only |
other multifamily buffer space | E.g., enclosed unconditioned stairwell | Average of conditioned space and outside; minimum of 50F | Attached/Multifamily only |
other non-freezing space | E.g., shared parking garage ceiling | Floats with outside; minimum of 40F | Attached/Multifamily only |
If the location is not provided, a default water heater location will be assumed based on IECC climate zone:
IECC Climate Zone | Location (default) |
---|---|
1-3, excluding 3A | garage if present, otherwise living space |
3A, 4-8, unknown | conditioned basement if present, otherwise unconditioned basement if present, otherwise living space |
The setpoint temperature may be provided as HotWaterTemperature
; if not provided, 125F is assumed.
The water heater may be optionally described as a shared system (i.e., serving multiple dwelling units or a shared laundry room) using IsSharedSystem
.
If not provided, it is assumed to be false.
If provided and true, NumberofUnitsServed
must also be specified, where the value is the number of dwelling units served either indirectly (e.g., via shared laundry room) or directly.
HPXML Hot Water Distribution¶
A single Systems/WaterHeating/HotWaterDistribution
must be provided if any water heating systems are specified.
Inputs including SystemType
and PipeInsulation/PipeRValue
must be provided.
Note: Any hot water distribution associated with a shared laundry room in attached/multifamily buildings should not be defined.
Standard¶
For a SystemType/Standard
(non-recirculating) system within the dwelling unit, the following element are used:
PipingLength
: Optional. Measured length of hot water piping from the hot water heater (or from a shared recirculation loop serving multiple dwelling units) to the farthest hot water fixture, measured longitudinally from plans, assuming the hot water piping does not run diagonally, plus 10 feet of piping for each floor level, plus 5 feet of piping for unconditioned basements (if any) If not provided, a defaultPipingLength
will be calculated using the following equation from ANSI/RESNET/ICC 301-2019.\[PipeL = 2.0 \cdot (\frac{CFA}{NCfl})^{0.5} + 10.0 \cdot NCfl + 5.0 \cdot bsmnt\]Where, PipeL = piping length [ft], CFA = conditioned floor area [ft²], NCfl = number of conditioned floor levels number of conditioned floor levels in the residence including conditioned basements, bsmnt = presence = 1.0 or absence = 0.0 of an unconditioned basement in the residence.
Recirculation¶
For a SystemType/Recirculation
system within the dwelling unit, the following elements are used:
ControlType
: One of “manual demand control”, “presence sensor demand control”, “temperature”, “timer”, or “no control”.RecirculationPipingLoopLength
: Optional. If not provided, the default value will be calculated by using the equation shown in the table below. Measured recirculation loop length including both supply and return sides, measured longitudinally from plans, assuming the hot water piping does not run diagonally, plus 20 feet of piping for each floor level greater than one plus 10 feet of piping for unconditioned basements.BranchPipingLoopLength
: Optional. If not provided, the default value will be assumed as shown in the table below. Measured length of the branch hot water piping from the recirculation loop to the farthest hot water fixture from the recirculation loop, measured longitudinally from plans, assuming the branch hot water piping does not run diagonally.PumpPower
: Optional. If not provided, the default value will be assumed as shown in the table below. Pump Power in Watts.Element Name Default Value RecirculationPipingLoopLength [ft] \(2.0 \cdot (2.0 \cdot (\frac{CFA}{NCfl})^{0.5} + 10.0 \cdot NCfl + 5.0 \cdot bsmnt) - 20.0\) BranchPipingLoopLength [ft] 10 Pump Power [W] 50
Drain Water Heat Recovery¶
In addition, a HotWaterDistribution/DrainWaterHeatRecovery
(DWHR) may be specified.
The DWHR system is defined by:
FacilitiesConnected
: ‘one’ if there are multiple showers and only one of them is connected to a DWHR; ‘all’ if there is one shower and it’s connected to a DWHR or there are two or more showers connected to a DWHREqualFlow
: ‘true’ if the DWHR supplies pre-heated water to both the fixture cold water piping and the hot water heater potable supply pipingEfficiency
: As rated and labeled in accordance with CSA 55.1
HPXML Water Fixtures¶
Water fixtures should be entered as Systems/WaterHeating/WaterFixture
elements.
Each fixture must have WaterFixtureType
and LowFlow
elements provided.
Fixtures should be specified as low flow if they are <= 2.0 gpm.
A WaterHeating/extension/WaterFixturesUsageMultiplier
can also be optionally provided that scales hot water usage; if not provided, it is assumed to be 1.0.
HPXML Solar Thermal¶
A solar hot water system can be entered as a Systems/SolarThermal/SolarThermalSystem
.
The SystemType
element must be ‘hot water’.
Solar hot water systems can be described with either simple or detailed inputs.
Simple Model¶
If using simple inputs, the following elements are used:
SolarFraction
: Portion of total conventional hot water heating load (delivered energy and tank standby losses). Can be obtained from Directory of SRCC OG-300 Solar Water Heating System Ratings or NREL’s System Advisor Model or equivalent.ConnectedTo
: Optional. If not specified, applies to all water heaters in the building. If specified, must point to aWaterHeatingSystem
.
Detailed Model¶
If using detailed inputs, the following elements are used:
CollectorArea
: in units of ft²CollectorLoopType
: ‘liquid indirect’ or ‘liquid direct’ or ‘passive thermosyphon’CollectorType
: ‘single glazing black’ or ‘double glazing black’ or ‘evacuated tube’ or ‘integrated collector storage’CollectorAzimuth
CollectorTilt
CollectorRatedOpticalEfficiency
: FRTA (y-intercept); see Directory of SRCC OG-100 Certified Solar Collector RatingsCollectorRatedThermalLosses
: FRUL (slope, in units of Btu/hr-ft²-R); see Directory of SRCC OG-100 Certified Solar Collector RatingsStorageVolume
: Optional. If not provided, the default value in gallons will be calculated as 1.5 * CollectorAreaConnectedTo
: Must point to aWaterHeatingSystem
. The connected water heater cannot be of type space-heating boiler or attached to a desuperheater.
HPXML Photovoltaics¶
Each solar electric (photovoltaic) system should be entered as a Systems/Photovoltaics/PVSystem
.
The following elements, some adopted from the PVWatts model, are required for each PV system:
Location
: ‘ground’ or ‘roof’ mountedModuleType
: ‘standard’, ‘premium’, or ‘thin film’Tracking
: ‘fixed’ or ‘1-axis’ or ‘1-axis backtracked’ or ‘2-axis’ArrayAzimuth
ArrayTilt
MaxPowerOutput
Inputs including InverterEfficiency
, SystemLossesFraction
, and YearModulesManufactured
can be optionally entered.
If InverterEfficiency
is not provided, the default value of 0.96 is assumed.
SystemLossesFraction
includes the effects of soiling, shading, snow, mismatch, wiring, degradation, etc.
If neither SystemLossesFraction
or YearModulesManufactured
are provided, a default value of 0.14 will be used.
If SystemLossesFraction
is not provided but YearModulesManufactured
is provided, SystemLossesFraction
will be calculated using the following equation.
The PV system may be optionally described as a shared system (i.e., serving multiple dwelling units) using IsSharedSystem
.
If not provided, it is assumed to be false.
If provided and true, the total number of bedrooms across all dwelling units served by the system must be entered as extension/NumberofBedroomsServed
.
PV generation will be apportioned to the dwelling unit using its number of bedrooms divided by the total number of bedrooms in the building.
HPXML Appliances¶
This section describes elements specified in HPXML’s Appliances
.
The Location
for each appliance can be optionally provided as one of the following:
Location | Description | Building Type |
---|---|---|
living space | Above-grade conditioned floor area | Any |
basement - conditioned | Below-grade conditioned floor area | Any |
basement - unconditioned | Any | |
garage | Single-family garage (not shared parking garage) | Any |
other housing unit | E.g., conditioned adjacent unit or corridor | Attached/Multifamily only |
other heated space | E.g., shared laundry/equipment space | Attached/Multifamily only |
other multifamily buffer space | E.g., enclosed unconditioned stairwell | Attached/Multifamily only |
other non-freezing space | E.g., shared parking garage ceiling | Attached/Multifamily only |
If the location is not specified, the appliance is assumed to be in the living space.
HPXML Clothes Washer¶
An Appliances/ClothesWasher
element can be specified; if not provided, a clothes washer will not be modeled.
Several EnergyGuide label inputs describing the efficiency of the appliance can be provided. If the complete set of efficiency inputs is not provided, the following default values representing a standard clothes washer from 2006 will be used.
Element Name | Default Value |
---|---|
IntegratedModifiedEnergyFactor [ft³/kWh-cyc] | 1.0 |
RatedAnnualkWh [kWh/yr] | 400 |
LabelElectricRate [$/kWh] | 0.12 |
LabelGasRate [$/therm] | 1.09 |
LabelAnnualGasCost [$] | 27.0 |
Capacity [ft³] | 3.0 |
LabelUsage [cyc/week] | 6 |
If ModifiedEnergyFactor
is provided instead of IntegratedModifiedEnergyFactor
, it will be converted using the following equation based on the Interpretation on ANSI/RESNET 301-2014 Clothes Washer IMEF.
An extension/UsageMultiplier
can also be optionally provided that scales energy and hot water usage; if not provided, it is assumed to be 1.0.
The clothes washer may be optionally described as a shared appliance (i.e., in a shared laundry room) using IsSharedAppliance
.
If not provided, it is assumed to be false.
If provided and true, AttachedToWaterHeatingSystem
must also be specified and must reference a shared water heater.
HPXML Clothes Dryer¶
An Appliances/ClothesDryer
element can be specified; if not provided, a clothes dryer will not be modeled.
The dryer’s FuelType
must be provided.
Several EnergyGuide label inputs describing the efficiency of the appliance can be provided. If the complete set of efficiency inputs is not provided, the following default values representing a standard clothes dryer from 2006 will be used.
Element Name | Default Value |
---|---|
CombinedEnergyFactor [lb/kWh] | 3.01 |
ControlType | timer |
If EnergyFactor
is provided instead of CombinedEnergyFactor
, it will be converted into CombinedEnergyFactor
using the following equation based on the Interpretation on ANSI/RESNET/ICC 301-2014 Clothes Dryer CEF.
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
The clothes dryer may be optionally described as a shared appliance (i.e., in a shared laundry room) using IsSharedAppliance
.
If not provided, it is assumed to be false.
HPXML Dishwasher¶
An Appliances/Dishwasher
element can be specified; if not provided, a dishwasher will not be modeled.
Several EnergyGuide label inputs describing the efficiency of the appliance can be provided. If the complete set of efficiency inputs is not provided, the following default values representing a standard dishwasher from 2006 will be used.
Element Name | Default Value |
---|---|
RatedAnnualkWh [kwh/yr] | 467 |
LabelElectricRate [$/kWh] | 0.12 |
LabelGasRate [$/therm] | 1.09 |
LabelAnnualGasCost [$] | 33.12 |
PlaceSettingCapacity [#] | 12 |
LabelUsage [cyc/week] | 4 |
If EnergyFactor
is provided instead of RatedAnnualkWh
, it will be converted into RatedAnnualkWh
using the following equation based on ANSI/RESNET/ICC 301-2014.
An extension/UsageMultiplier
can also be optionally provided that scales energy and hot water usage; if not provided, it is assumed to be 1.0.
The dishwasher may be optionally described as a shared appliance (i.e., in a shared laundry room) using IsSharedAppliance
.
If not provided, it is assumed to be false.
If provided and true, AttachedToWaterHeatingSystem
must also be specified and must reference a shared water heater.
HPXML Refrigerators¶
Multiple Appliances/Refrigerator
elements can be specified; if none are provided, refrigerators will not be modeled.
The efficiency of the refrigerator can be optionally entered as RatedAnnualkWh
or extension/AdjustedAnnualkWh
.
If neither are provided, RatedAnnualkWh
will be defaulted to represent a standard refrigerator from 2006 using the following equation based on ANSI/RESNET/ICC 301-2019.
Optional extension/WeekdayScheduleFractions
, extension/WeekendScheduleFractions
, and extension/MonthlyScheduleMultipliers
can be provided; if not provided, values from Figures 16 & 24 of the Building America House Simulation Protocols are used.
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
If multiple refrigerators are specified, there must be exactly one refrigerator described with PrimaryIndicator='true'
.
The Location
of a primary refrigerator is described in the Appliances section.
If Location
is not provided for a non-primary refrigerator, its location will be chosen based on the presence of spaces and the “Default Priority” indicated below.
Location | Default Priority |
---|---|
garage | 1 |
basement - unconditioned | 2 |
basement - conditioned | 3 |
living space | 4 |
HPXML Freezers¶
Multiple Appliances/Freezer
elements can be provided; if none provided, standalone freezers will not be modeled.
The efficiency of the freezer can be optionally entered as RatedAnnualkWh or extension/AdjustedAnnualkWh. If neither are provided, RatedAnnualkWh will be defaulted to represent a benchmark freezer according to the Building America House Simulation Protocols (319.8 kWh/year).
Optional extension/WeekdayScheduleFractions
, extension/WeekendScheduleFractions
, and extension/MonthlyScheduleMultipliers
can be provided; if not provided, values from Figures 16 & 24 of the Building America House Simulation Protocols are used.
An extension/UsageMultiplier can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
HPXML Cooking Range/Oven¶
Appliances/CookingRange
and Appliances/Oven
elements can be specified; if not provided, a range/oven will not be modeled.
The FuelType
of the range must be provided.
Inputs including CookingRange/IsInduction
and Oven/IsConvection
can be optionally provided.
The following default values will be assumed unless a complete set of the optional variables is provided.
Element Name | Default Value |
---|---|
IsInduction | false |
IsConvection | false |
Optional CookingRange/extension/WeekdayScheduleFractions
, CookingRange/extension/WeekendScheduleFractions
, and CookingRange/extension/MonthlyScheduleMultipliers
can be provided; if not provided, values from Figures 22 & 24 of the Building America House Simulation Protocols are used.
An CookingRange/extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
HPXML Dehumidifier¶
An Appliance/Dehumidifier
element can be specified; if not provided, a dehumidifier will not be modeled.
The Capacity
, DehumidistatSetpoint
(relative humidity as a fraction, 0-1), and FractionDehumidificationLoadServed
(0-1) must be provided.
The efficiency of the dehumidifier can either be entered as an IntegratedEnergyFactor
or EnergyFactor
.
HPXML Lighting¶
This section describes elements specified in HPXML’s Lighting
.
HPXML Lighting Groups¶
The building’s lighting is described by nine LightingGroup
elements, each of which is the combination of:
LightingType
: ‘LightEmittingDiode’, ‘CompactFluorescent’, and ‘FluorescentTube’Location
: ‘interior’, ‘garage’, and ‘exterior’
The fraction of lamps of the given type in the given location are provided as the LightingGroup/FractionofUnitsInLocation
.
The fractions for a given location cannot sum to greater than 1.
If the fractions sum to less than 1, the remainder is assumed to be incandescent lighting.
Garage lighting values are ignored if the building has no garage.
Optional extension/InteriorUsageMultiplier
, extension/ExteriorUsageMultiplier
, and extension/GarageUsageMultiplier
can be provided that scales energy usage; if not provided, they are assumed to be 1.0.
An optional extension/ExteriorHolidayLighting
can also be provided to define additional exterior holiday lighting; if not provided, none will be modeled.
If provided, child elements Load[Units='kWh/day']/Value
, PeriodBeginMonth
/PeriodBeginDayOfMonth
, PeriodEndMonth
/PeriodEndDayOfMonth
, WeekdayScheduleFractions
, and WeekendScheduleFractions
can be optionally provided.
For the child elements not provided, the following default values will be used.
Element Name | Default Value |
---|---|
Load[Units=’kWh/day’]/Value | 1.1 for single-family detached and 0.55 for others |
PeriodBeginMonth/PeriodBeginDayOfMonth | 11/24 (November 24) |
PeriodEndMonth/PeriodEndDayOfMonth | 1/6 (January 6) |
WeekdayScheduleFractions | 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0.008, 0.098, 0.168, 0.194, 0.284, 0.192, 0.037, 0.019 |
WeekendScheduleFractions | 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0, 0.008, 0.098, 0.168, 0.194, 0.284, 0.192, 0.037, 0.019 |
Finally, optional schedules can be defined:
- Interior: Optional
extension/InteriorWeekdayScheduleFractions
,extension/InteriorWeekendScheduleFractions
, andextension/InteriorMonthlyScheduleMultipliers
can be provided; if not provided, values will be calculated using Lighting Calculation Option 2 (location-dependent lighting profile) of the Building America House Simulation Protocols. - Garage: Optional
extension/GarageWeekdayScheduleFractions
,extension/GarageWeekendScheduleFractions
, andextension/GarageMonthlyScheduleMultipliers
can be provided; if not provided, values from Appendix C Table 8 of the Title 24 2016 Residential Alternative Calculation Method Reference Manual are used. - Exterior: Optional
extension/ExteriorWeekdayScheduleFractions
,extension/ExteriorWeekendScheduleFractions
, andextension/ExteriorMonthlyScheduleMultipliers
can be provided; if not provided, values from Appendix C Table 8 of the Title 24 2016 Residential Alternative Calculation Method Reference Manual are used.
HPXML Ceiling Fans¶
Each ceiling fan (or set of identical ceiling fans) should be entered as a CeilingFan
.
The Airflow/Efficiency
(at medium speed) and Quantity
can be provided, otherwise the following default assumptions are used from ANSI/RESNET/ICC 301-2019.
Element Name | Default Value |
---|---|
Airflow/Efficiency [cfm/W] | 3000/42.6 |
Quantity [#] | NumberofBedrooms+1 |
In addition, a reduced cooling setpoint can be specified for summer months when ceiling fans are operating. See the Thermostat section for more information.
HPXML Pool¶
A Pools/Pool
element can be specified; if not provided, a pool will not be modeled.
A PoolPumps/PoolPump
element is required.
The annual energy consumption of the pool pump (Load[Units='kWh/year']/Value
) can be provided, otherwise they will be calculated using the following equation based on the Building America House Simulation Protocols.
A Heater
element can be specified; if not provided, a pool heater will not be modeled.
Currently only pool heaters specified with Heater[Type='gas fired' or Type='electric resistance' or Type='heat pump']
are recognized.
The annual energy consumption (Load[Units='kWh/year' or Units='therm/year']/Value
) can be provided, otherwise they will be calculated using the following equations from the Building America House Simulation Protocols.
A PoolPump/extension/UsageMultiplier
can also be optionally provided that scales pool pump energy usage; if not provided, it is assumed to be 1.0.
A Heater/extension/UsageMultiplier
can also be optionally provided that scales pool heater energy usage; if not provided, it is assumed to be 1.0.
Optional extension/WeekdayScheduleFractions
, extension/WeekendScheduleFractions
, and extension/MonthlyScheduleMultipliers
can be provided for HotTubPump
and Heater
; if not provided, values from Figures 23 & 24 of the Building America House Simulation Protocols are used.
HPXML Hot Tub¶
A HotTubs/HotTub
element can be specified; if not provided, a hot tub will not be modeled.
A HotTubPumps/HotTubPump
element is required.
The annual energy consumption of the hot tub pump (Load[Units='kWh/year']/Value
) can be provided, otherwise they will be calculated using the following equation based on the Building America House Simulation Protocols.
A Heater
element can be specified; if not provided, a hot tub heater will not be modeled.
Currently only hot tub heaters specified with Heater[Type='gas fired' or Type='electric resistance' or Type='heat pump']
are recognized.
The annual energy consumption (Load[Units='kWh/year' or Units='therm/year']/Value
) can be provided, otherwise they will be calculated using the following equations from the Building America House Simulation Protocols.
A HotTubPump/extension/UsageMultiplier
can also be optionally provided that scales hot tub pump energy usage; if not provided, it is assumed to be 1.0.
A Heater/extension/UsageMultiplier
can also be optionally provided that scales hot tub heater energy usage; if not provided, it is assumed to be 1.0.
Optional extension/WeekdayScheduleFractions
, extension/WeekendScheduleFractions
, and extension/MonthlyScheduleMultipliers
can be provided for PoolPump
and Heater
; if not provided, values from Figures 23 & 24 of the Building America House Simulation Protocols are used.
HPXML Misc Loads¶
This section describes elements specified in HPXML’s MiscLoads
.
HPXML Plug Loads¶
Misc electric plug loads can be provided by entering PlugLoad
elements.
Currently only plug loads specified with PlugLoadType='other'
, PlugLoadType='TV other'
, PlugLoadType='electric vehicle charging'
, or PlugLoadType='well pump'
are recognized.
The ‘other’ and ‘TV other’ plug loads are required to represent the typical home; the other less common plug loads will only be modeled if provided.
The annual energy consumption (Load[Units='kWh/year']/Value
), Location
, extension/FracSensible
, and extension/FracLatent
elements are optional.
If not provided, they will be defaulted as follows.
Annual energy consumption equations are based on ANSI/RESNET/ICC 301-2019 or the Building America House Simulation Protocols.
Plug Load Type | kWh/year | Location | FracSensible | FracLatent |
---|---|---|---|---|
other | 0.91*CFA | interior | 0.855 | 0.045 |
TV other | 413.0 + 69.0*NBr | interior | 1.0 | 0.0 |
electric vehicle charging | 1666.67 | exterior | 0.0 | 0.0 |
well pump | 50.8/0.127*(0.5 + 0.25*NBr/3 + 0.35*CFA/1920) | exterior | 0.0 | 0.0 |
where CFA is the conditioned floor area and NBr is the number of bedrooms.
The electric vehicle charging default kWh/year is calculated using:
where AnnualMiles=4500, kWhPerMile=0.3, EVChargerEfficiency=0.9, and EVBatteryEfficiency=0.9.
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
Optional extension/WeekdayScheduleFractions
, extension/WeekendScheduleFractions
, and extension/MonthlyScheduleMultipliers
can be provided.
If not provided, values from Figures 23 & 24 of the Building America House Simulation Protocols are used for PlugLoadType='other'
, PlugLoadType='electric vehicle charging'
, and PlugLoadType='well pump'
; values from the American Time Use Survey are used for PlugLoadType='TV other'
.
HPXML Fuel Loads¶
Misc fuel loads can be provided by entering FuelLoad
elements.
Currently only fuel loads specified with FuelLoadType='grill'
, FuelLoadType='lighting'
, or FuelLoadType='fireplace'
are recognized.
These less common fuel loads will only be modeled if provided.
The annual energy consumption (Load[Units='therm/year']/Value
), Location
, extension/FracSensible
, and extension/FracLatent
elements are also optional.
If not provided, they will be defaulted as follows.
Annual energy consumption equations are based on the Building America House Simulation Protocols.
Plug Load Type | therm/year | Location | FracSensible | FracLatent |
---|---|---|---|---|
grill | 0.87/0.029*(0.5 + 0.25*NBr/3 + 0.35*CFA/1920) | exterior | 0.0 | 0.0 |
lighting | 0.22/0.012*(0.5 + 0.25*NBr/3 + 0.35*CFA/1920) | exterior | 0.0 | 0.0 |
fireplace | 1.95/0.032*(0.5 + 0.25*NBr/3 + 0.35*CFA/1920) | interior | 0.5 | 0.1 |
where CFA is the conditioned floor area and NBr is the number of bedrooms.
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
Optional extension/WeekdayScheduleFractions
, extension/WeekendScheduleFractions
, and extension/MonthlyScheduleMultipliers
can be provided; if not provided, values from Figures 23 & 24 of the Building America House Simulation Protocols are used.
Validating & Debugging Errors¶
When running HPXML files, errors may occur because:
- An HPXML file provided is invalid (either relative to the HPXML schema or the EnergyPlus Use Case).
- An unexpected EnergyPlus simulation error occurred.
If an error occurs, first look in the run.log for details. If there are no errors in that log file, then the error may be in the EnergyPlus simulation – see eplusout.err.
Contact us if you can’t figure out the cause of an error.
Sample Files¶
Dozens of sample HPXML files are included in the workflow/sample_files directory. The sample files help to illustrate how different building components are described in HPXML.
Each sample file generally makes one isolated change relative to the base HPXML (base.xml) building.
For example, the base-dhw-dwhr.xml file adds a DrainWaterHeatRecovery
element to the building.
You may find it useful to search through the files for certain HPXML elements or compare (diff) a sample file to the base.xml file.