HPXMLtoOpenStudio Measure¶
The HPXMLtoOpenStudio measure requires a building description in an HPXML file format. HPXML is an open data standard for collecting and transferring home energy data. Using HPXML files reduces the complexity and effort for software developers to leverage the EnergyPlus simulation engine.
Capabilities¶
The following building features/technologies are available for modeling via the HPXMLtoOpenStudio measure:
- Enclosure
- Attics (Vented, Unvented, Conditioned)
- Foundations (Slab, Unconditioned Basement, Conditioned Basement, Vented Crawlspace, Unvented Crawlspace, Ambient)
- Garages
- Windows & Overhangs
- Skylights
- Doors
- HVAC
- Heating Systems (Electric Resistance, Furnaces, Wall Furnaces, Stoves, Boilers, Portable Heaters)
- Cooling Systems (Central Air Conditioners, Room Air Conditioners, Evaporative Coolers)
- Heat Pumps (Air Source, Mini Split, Ground Source, Dual-Fuel)
- Setpoints
- Ducts
- Water Heating
- Water Heaters (Storage, Tankless, Heat Pump, Indirect, Tankless Coil)
- Solar Hot Water
- Desuperheater
- Hot Water Distribution (Standard, Recirculation)
- Drain Water Heat Recovery
- Hot Water Fixtures
- Ventilation
- Mechanical Ventilation (Exhaust, Supply, Balanced, ERV, HRV, CFIS)
- Kitchen/Bathroom Fans
- Whole House Fan
- Photovoltaics
- Appliances (Clothes Washer/Dryer, Dishwasher, Refrigerator, Cooking Range/Oven)
- Dehumidifier
- Lighting
- Ceiling Fans
- Plug Loads
EnergyPlus Use Case for HPXML¶
HPXML is an flexible and extensible format, where nearly all elements in the schema are optional and custom elements can be included. Because of this, an EnergyPlus Use Case for HPXML has been developed that specifies the HPXML elements or enumeration choices required to run the measure.
Software developers should use the EnergyPlus Use Case (found at HPXMLtoOpenStudio/resources/EPvalidator.rb
, which defines sets of conditional XPath expressions) as well as the HPXML schema (HPXML.xsd) to construct valid HPXML files for EnergyPlus simulations.
The HPXML Toolbox website also provides several resources for software developers, including:
- An interactive schema validator
- A data dictionary
- An implementation guide
Simulation Controls¶
EnergyPlus simulation controls can be entered in /HPXML/SoftwareInfo/extension/SimulationControl
.
The simulation controls currently offered are timestep, begin month, begin day of month, end month, and end day of month.
Timestep can be optionally provided as Timestep
, where the value is in minutes and must be a divisor of 60.
If not provided, the default value of 60 is used.
The simulation run period can be optionally specified with BeginMonth
/BeginDayOfMonth
and/or EndMonth
/EndDayOfMonth
.
The BeginMonth
/BeginDayOfMonth
provided must occur before EndMonth
/EndDayOfMonth
provided (e.g., a run period from 10/1 to 3/31 is invalid).
If not provided, default values of January 1st and December 31st will be used.
Building Details¶
The building description is entered in HPXML’s /HPXML/Building/BuildingDetails
.
Building Summary¶
This section describes elements specified in HPXML’s BuildingSummary
.
It is used for high-level building information including conditioned floor area, number of bedrooms, number of residents, number of conditioned floors, etc.
Most occupancy assumptions are based on the number of bedrooms, while the number of residents is solely used to determine heat gains from the occupants themselves.
Note that a walkout basement should be included in NumberofConditionedFloorsAboveGrade
.
If NumberofBathrooms
is not provided, it is calculated using the following equation based on the Building America House Simulation Protocols.
Shading due to neighboring buildings can be defined inside an Site/extension/Neighbors
element.
Each Neighbors/NeighborBuilding
element is required to have an Azimuth
and Distance
from the house.
A Height
is also optionally allowed; if not provided, the neighbor is assumed to be the same height as the house.
The local shelter coefficient can be entered as Site/extension/ShelterCoefficient
.
The shelter coefficient is defined by the AIM-2 infiltration model to account for nearby buildings, trees and obstructions.
If not provided, the value of 0.5 will be assumed.
Shelter Coefficient | Description |
---|---|
1.0 | No obstructions or local shielding |
0.9 | Light local shielding with few obstructions within two building heights |
0.7 | Local shielding with many large obstructions within two building heights |
0.5 | Heavily shielded, many large obstructions within one building height |
0.3 | Complete shielding with large buildings immediately adjacent |
The terrain surrounding the building is assumed to be suburban.
Weather File¶
The ClimateandRiskZones/WeatherStation
element specifies the EnergyPlus weather file (EPW) to be used in the simulation.
The weather file can be entered in one of two ways:
- Using
WeatherStation/WMO
, which must be one of the acceptable TMY3 WMO station numbers found in theweather/data.csv
file. The full set of U.S. TMY3 weather files can be downloaded here. - Using
WeatherStation/extension/EPWFilePath
.
Enclosure¶
This section describes elements specified in HPXML’s Enclosure
.
All surfaces that bound different space types in the building (i.e., not just thermal boundary surfaces) must be specified in the HPXML file. For example, an attached garage would generally be defined by walls adjacent to conditioned space, walls adjacent to outdoors, a slab, and a roof or ceiling. For software tools that do not collect sufficient inputs for every required surface, the software developers will need to make assumptions about these surfaces or collect additional input.
The space types used in the HPXML building description are:
Space Type | Notes |
---|---|
living space | Above-grade conditioned floor area. |
attic - vented | |
attic - unvented | |
basement - conditioned | Below-grade conditioned floor area. |
basement - unconditioned | |
crawlspace - vented | |
crawlspace - unvented | |
garage | |
other housing unit | Used to specify adiabatic surfaces. |
Warning
It is the software tool’s responsibility to provide the appropriate building surfaces. While some error-checking is in place, it is not possible to know whether some surfaces are incorrectly missing.
Also note that wall and roof surfaces do not require an azimuth to be specified. Rather, only the windows/skylights themselves require an azimuth. Thus, software tools can choose to use a single wall (or roof) surface to represent multiple wall (or roof) surfaces for the entire building if all their other properties (construction type, interior/exterior adjacency, etc.) are identical.
Air Leakage¶
Building air leakage characterized by air changes per hour or cfm at 50 pascals pressure difference (ACH50 or CFM50) is entered at Enclosure/AirInfiltration/AirInfiltrationMeasurement/BuildingAirLeakage/AirLeakage
.
The Enclosure/AirInfiltration/AirInfiltrationMeasurement
should be specified with HousePressure='50'
and BuildingAirLeakage/UnitofMeasure='ACH'
or BuildingAirLeakage/UnitofMeasure='CFM'
.
In addition, the building’s volume associated with the air leakage measurement can be provided in HPXML’s AirInfiltrationMeasurement/InfiltrationVolume
.
If not provided, the infiltration volume is assumed to be equal to the conditioned building volume.
Vented Attics/Crawlspaces¶
The ventilation rate for vented attics (or crawlspaces) can be specified using an Attic
(or Foundation
) element.
First, define the AtticType
as Attic[Vented='true']
(or FoundationType
as Crawlspace[Vented='true']
).
Then use the VentilationRate[UnitofMeasure='SLA']/Value
element to specify a specific leakage area (SLA).
If these elements are not provided, default values of 1/300 for vented attics and 1/150 for vented crawlspaces will be used based on ANSI/RESNET/ICC 301-2019.
Roofs¶
Pitched or flat roof surfaces that are exposed to ambient conditions should be specified as an Enclosure/Roofs/Roof
.
For a multifamily building where the dwelling unit has another dwelling unit above it, the surface between the two dwelling units should be considered a FrameFloor
and not a Roof
.
Beyond the specification of typical heat transfer properties (insulation R-value, solar absorptance, emittance, etc.), note that roofs can be defined as having a radiant barrier.
Walls¶
Any wall that has no contact with the ground and bounds a space type should be specified as an Enclosure/Walls/Wall
.
Interior walls (for example, walls solely within the conditioned space of the building) are not required.
Walls are primarily defined by their Insulation/AssemblyEffectiveRValue
.
The choice of WallType
has a secondary effect on heat transfer in that it informs the assumption of wall thermal mass.
Rim Joists¶
Rim joists, the perimeter of floor joists typically found between stories of a building or on top of a foundation wall, are specified as an Enclosure//RimJoists/RimJoist
.
The InteriorAdjacentTo
element should typically be “living space” for rim joists between stories of a building and “basement - conditioned”, “basement - unconditioned”, “crawlspace - vented”, or “crawlspace - unvented” for rim joists on top of a foundation wall.
Foundation Walls¶
Any wall that is in contact with the ground should be specified as an Enclosure/FoundationWalls/FoundationWall
.
Other walls (e.g., wood framed walls) that are connected to a below-grade space but have no contact with the ground should be specified as Walls
and not FoundationWalls
.
Exterior foundation walls (i.e., those that fall along the perimeter of the building’s footprint) should use “ground” for ExteriorAdjacentTo
and the appropriate space type (e.g., “basement - unconditioned”) for InteriorAdjacentTo
.
Interior foundation walls should be specified with two appropriate space types (e.g., “crawlspace - vented” and “garage”, or “basement - unconditioned” and “crawlspace - unvented”) for InteriorAdjacentTo
and ExteriorAdjacentTo
.
Interior foundation walls should never use “ground” for ExteriorAdjacentTo
even if the foundation wall has some contact with the ground due to the difference in below-grade depths of the two adjacent space types.
Foundations must include a Height
as well as a DepthBelowGrade
.
For exterior foundation walls, the depth below grade is relative to the ground plane.
For interior foundation walls, the depth below grade should not be thought of as relative to the ground plane, but rather as the depth of foundation wall in contact with the ground.
For example, an interior foundation wall between an 8 ft conditioned basement and a 3 ft crawlspace has a height of 8 ft and a depth below grade of 5 ft.
Alternatively, an interior foundation wall between an 8 ft conditioned basement and an 8 ft unconditioned basement has a height of 8 ft and a depth below grade of 0 ft.
Foundation wall insulation can be described in two ways:
Option 1. Both interior and exterior continuous insulation layers with NominalRValue
, extension/DistanceToTopOfInsulation
, and extension/DistanceToBottomOfInsulation
.
Insulation layers are particularly useful for describing foundation wall insulation that doesn’t span the entire height (e.g., 4 ft of insulation for an 8 ft conditioned basement).
If there is not insulation on the interior and/or exterior of the foundation wall, the continuous insulation layer must still be provided – with the nominal R-value, etc., set to zero.
When insulation is specified with option 1, it is modeled with a concrete wall (whose Thickness
is provided) as well as air film resistances as appropriate.
Option 2. An AssemblyEffectiveRValue
.
The assembly effective R-value should include the concrete wall and an interior air film resistance.
The exterior air film resistance (for any above-grade exposure) or any soil thermal resistance should not be included.
Frame Floors¶
Any horizontal floor/ceiling surface that is not in contact with the ground (Slab) nor adjacent to ambient conditions above (Roof) should be specified as an Enclosure/FrameFloors/FrameFloor
.
Frame floors are primarily defined by their Insulation/AssemblyEffectiveRValue
.
Slabs¶
Any space type that borders the ground should include an Enclosure/Slabs/Slab
surface with the appropriate InteriorAdjacentTo
.
This includes basements, crawlspaces (even when there are dirt floors – use zero for the Thickness
), garages, and slab-on-grade foundations.
A primary input for a slab is its ExposedPerimeter
.
The exposed perimeter should include any slab length that falls along the perimeter of the building’s footprint (i.e., is exposed to ambient conditions).
So, a basement slab edge adjacent to a garage or crawlspace, for example, should not be included.
Vertical insulation adjacent to the slab can be described by a PerimeterInsulation/Layer/NominalRValue
and a PerimeterInsulationDepth
.
Horizontal insulation under the slab can be described by a UnderSlabInsulation/Layer/NominalRValue
.
The insulation can either have a fixed width (UnderSlabInsulationWidth
) or can span the entire slab (UnderSlabInsulationSpansEntireSlab
).
For foundation types without walls, the DepthBelowGrade
element must be provided.
For foundation types with walls, the DepthBelowGrade
element is not used; instead the slab’s position relative to grade is determined by the FoundationWall/DepthBelowGrade
values.
Windows¶
Any window or glass door area should be specified as an Enclosure/Windows/Window
.
Windows are defined by full-assembly NFRC UFactor
and SHGC
, as well as Area
.
Windows must reference a HPXML Enclosures/Walls/Wall
element via the AttachedToWall
.
Windows must also have an Azimuth
specified, even if the attached wall does not.
In addition, the summer/winter interior shading coefficients can be optionally entered as InteriorShading/SummerShadingCoefficient
and InteriorShading/WinterShadingCoefficient
.
The summer interior shading coefficient must be less than or equal to the winter interior shading coefficient.
Note that a value of 0.7 indicates a 30% reduction in solar gains (i.e., 30% shading).
If not provided, default values of 0.70 for summer and 0.85 for winter will be used based on ANSI/RESNET/ICC 301-2019.
Overhangs (e.g., a roof eave) can optionally be defined for a window by specifying a Window/Overhangs
element.
Overhangs are defined by the vertical distance between the overhang and the top of the window (DistanceToTopOfWindow
), and the vertical distance between the overhang and the bottom of the window (DistanceToBottomOfWindow
).
The difference between these two values equals the height of the window.
Finally, windows can be optionally described with FractionOperable
.
The input should solely reflect whether the windows are operable (can be opened), not how they are used by the occupants.
If a Window
represents a single window, the value should be 0 or 1.
If a Window
represents multiple windows (e.g., 4), the value should be between 0 and 1 (e.g., 0, 0.25, 0.5, 0.75, or 1).
If not provided, it is assumed that 67% of the windows are operable.
The total open window area for natural ventilation is thus calculated using A) the fraction of windows that are operable, B) the assumption that 50% of the area of operable windows can be open, and C) the assumption that 20% of that openable area is actually opened by occupants whenever outdoor conditions are favorable for cooling.
Skylights¶
Any skylight should be specified as an Enclosure/Skylights/Skylight
.
Skylights are defined by full-assembly NFRC UFactor
and SHGC
, as well as Area
.
Skylights must reference a HPXML Enclosures/Roofs/Roof
element via the AttachedToRoof
.
Skylights must also have an Azimuth
specified, even if the attached roof does not.
Doors¶
Any opaque doors should be specified as an Enclosure/Doors/Door
.
Doors are defined by RValue
and Area
.
Doors must reference a HPXML Enclosures/Walls/Wall
element via the AttachedToWall
.
Doors must also have an Azimuth
specified, even if the attached wall does not.
Systems¶
This section describes elements specified in HPXML’s Systems
.
If any HVAC systems are entered that provide heating (or cooling), the sum of all their FractionHeatLoadServed
(or FractionCoolLoadServed
) values must be less than or equal to 1.
For example, a room air conditioner might be specified with FractionCoolLoadServed
equal to 0.3 if it serves 30% of the home’s conditioned floor area.
If any water heating systems are entered, the sum of all their FractionDHWLoadServed
values must be equal to 1.
Note
HVAC systems (Heating Systems, Cooling Systems, and Heat Pumps) can be autosized via ACCA Manual J/S by using -1 as the capacity. For a given system, all capacities must either be autosized or user-specified. For example, an air-to-air heat pump must have its heating capacity, cooling capacity, and backup heating capacity all autosized or user-specified.
Heating Systems¶
Each heating system (other than heat pumps) should be entered as a Systems/HVAC/HVACPlant/HeatingSystem
.
Inputs including HeatingSystemType
, HeatingCapacity
, and FractionHeatLoadServed
must be provided.
Depending on the type of heating system specified, additional elements are required:
HeatingSystemType | DistributionSystem | HeatingSystemFuel | AnnualHeatingEfficiency |
---|---|---|---|
ElectricResistance | electricity | Percent | |
Furnace | AirDistribution or DSE | <any> | AFUE |
WallFurnace | <any> | AFUE | |
Boiler | HydronicDistribution or DSE | <any> | AFUE |
Stove | <any> | Percent | |
PortableHeater | <any> | Percent |
If a non-electric heating system is specified, the ElectricAuxiliaryEnergy
element may be provided if available.
Cooling Systems¶
Each cooling system (other than heat pumps) should be entered as a Systems/HVAC/HVACPlant/CoolingSystem
.
Inputs including CoolingSystemType
and FractionCoolLoadServed
must be provided.
CoolingCapacity
must also be provided for all systems other than evaporative coolers.
Depending on the type of cooling system specified, additional elements are required/available:
CoolingSystemType | DistributionSystem | CoolingSystemFuel | AnnualCoolingEfficiency | SensibleHeatFraction |
---|---|---|---|---|
central air conditioner | AirDistribution or DSE | electricity | SEER | (optional) |
room air conditioner | electricity | EER | (optional) | |
evaporative cooler | AirDistribution or DSE (optional) | electricity |
Central air conditioners can also have the CompressorType
specified; if not provided, it is assumed as follows:
- “single stage”: SEER <= 15
- “two stage”: 15 < SEER <= 21
- “variable speed”: SEER > 21
Heat Pumps¶
Each heat pump should be entered as a Systems/HVAC/HVACPlant/HeatPump
.
Inputs including HeatPumpType
, CoolingCapacity
, HeatingCapacity
, FractionHeatLoadServed
, and FractionCoolLoadServed
must be provided.
Note that heat pumps are allowed to provide only heating (FractionCoolLoadServed
= 0) or cooling (FractionHeatLoadServed
= 0) if appropriate.
Depending on the type of heat pump specified, additional elements are required/available:
HeatPumpType | DistributionSystem | HeatPumpFuel | AnnualCoolingEfficiency | AnnualHeatingEfficiency | CoolingSensibleHeatFraction | HeatingCapacity17F |
---|---|---|---|---|---|---|
air-to-air | AirDistribution or DSE | electricity | SEER | HSPF | (optional) | (optional) |
mini-split | AirDistribution or DSE (optional) | electricity | SEER | HSPF | (optional) | (optional) |
ground-to-air | AirDistribution or DSE | electricity | EER | COP | (optional) |
Air-to-air heat pumps can also have the CompressorType
specified; if not provided, it is assumed as follows:
- “single stage”: SEER <= 15
- “two stage”: 15 < SEER <= 21
- “variable speed”: SEER > 21
If the heat pump has backup heating, it can be specified with BackupSystemFuel
, BackupAnnualHeatingEfficiency
, and BackupHeatingCapacity
.
If the heat pump has a switchover temperature (e.g., dual-fuel heat pump) where the heat pump stops operating and the backup heating system starts running, it can be specified with BackupHeatingSwitchoverTemperature
.
If the BackupHeatingSwitchoverTemperature
is not provided, the backup heating system will operate as needed when the heat pump has insufficient capacity.
Thermostat¶
A Systems/HVAC/HVACControl
must be provided if any HVAC systems are specified.
The heating setpoint (SetpointTempHeatingSeason
) and cooling setpoint (SetpointTempCoolingSeason
) are required elements.
If there is a heating setback, it is defined with:
SetbackTempHeatingSeason
: Temperature during heating setbackextension/SetbackStartHourHeating
: The start hour of the heating setback where 0=midnight and 12=noonTotalSetbackHoursperWeekHeating
: The number of hours of heating setback per week
If there is a cooling setup, it is defined with:
SetupTempCoolingSeason
: Temperature during cooling setupextension/SetupStartHourCooling
: The start hour of the cooling setup where 0=midnight and 12=noonTotalSetupHoursperWeekCooling
: The number of hours of cooling setup per week
Finally, if there are sufficient ceiling fans present that result in a reduced cooling setpoint, this offset can be specified with extension/CeilingFanSetpointTempCoolingSeasonOffset
.
HVAC Distribution¶
Each separate HVAC distribution system should be specified as a Systems/HVAC/HVACDistribution
.
There should be at most one heating system and one cooling system attached to a distribution system.
See the sections on Heating Systems, Cooling Systems, and Heat Pumps for information on which DistributionSystemType
is allowed for which HVAC system.
Also, note that some HVAC systems (e.g., room air conditioners) are not allowed to be attached to a distribution system.
AirDistribution
systems are defined by:
- Supply leakage to the outside in CFM25 or percent of airflow (
DuctLeakageMeasurement[DuctType='supply']/DuctLeakage/Value
) - Optional return leakage to the outside in CFM25 or percent of airflow (
DuctLeakageMeasurement[DuctType='return']/DuctLeakage/Value
) - Optional supply ducts (
Ducts[DuctType='supply']
) - Optional return ducts (
Ducts[DuctType='return']
)
For each duct, DuctInsulationRValue
, DuctLocation
, and DuctSurfaceArea
must be provided.
HydronicDistribution
systems do not require any additional inputs.
DSE
systems are defined by a AnnualHeatingDistributionSystemEfficiency
and AnnualCoolingDistributionSystemEfficiency
elements.
Warning
Specifying a DSE for the HVAC distribution system will NOT be reflected in the raw EnergyPlus simulation outputs, but IS reflected by the SimulationOutputReport reporting measure.
Mechanical Ventilation¶
A single whole-house mechanical ventilation system may be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with UsedForWholeBuildingVentilation='true'
.
Inputs including FanType
, TestedFlowRate
(or RatedFlowRate
), HoursInOperation
, and FanPower
must be provided.
Depending on the type of mechanical ventilation specified, additional elements are required:
FanType | SensibleRecoveryEfficiency | TotalRecoveryEfficiency | AttachedToHVACDistributionSystem |
---|---|---|---|
energy recovery ventilator | required | required | |
heat recovery ventilator | required | ||
exhaust only | |||
supply only | |||
balanced | |||
central fan integrated supply (CFIS) | required |
Note that AdjustedSensibleRecoveryEfficiency and AdjustedTotalRecoveryEfficiency can be provided instead.
In many situations, the rated flow rate should be the value derived from actual testing of the system. For a CFIS system, the rated flow rate should equal the amount of outdoor air provided to the distribution system.
Kitchen Fan¶
A kitchen range fan may be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with FanLocation='kitchen'
and UsedForLocalVentilation='true'
.
Additional fields may be provided per the table below. If not provided, default values will be assumed based on the Building America House Simulation Protocols.
Element Name | Default Value |
---|---|
RatedFlowRate [cfm] | 100 |
HoursInOperation [hrs/day] | 1 |
FanPower [W] | 0.3 * RatedFlowRate |
extension/StartHour [0-23] | 18 |
Bathroom Fans¶
Bathroom fans may be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with FanLocation='bath'
and UsedForLocalVentilation='true'
.
Additional fields may be provided per the table below. If not provided, default values will be assumed based on the Building America House Simulation Protocols.
Element Name | Default Value |
---|---|
Quantity [#] | NumberofBathrooms |
RatedFlowRate [cfm] | 50 |
HoursInOperation [hrs/day] | 1 |
FanPower [W] | 0.3 * RatedFlowRate |
extension/StartHour [0-23] | 7 |
Whole House Fan¶
A single whole house fan may be specified as a Systems/MechanicalVentilation/VentilationFans/VentilationFan
with UsedForSeasonalCoolingLoadReduction='true'
.
Required elements include RatedFlowRate
and FanPower
.
The whole house fan is assumed to operate during hours of favorable outdoor conditions. If available, it will take priority over natural ventilation.
Water Heaters¶
Each water heater should be entered as a Systems/WaterHeating/WaterHeatingSystem
.
Inputs including WaterHeaterType
and FractionDHWLoadServed
must be provided.
The water heater Location
can be optionally entered; if not provided, a default water heater location will be assumed based on IECC climate zone.
IECC Climate Zone | Default Water Heater Location |
---|---|
1-3, excluding 3A | Garage if present, else Living Space |
3A, 4-8, unknown | Conditioned Basement if present, else Unconditioned Basement if present, else Living Space |
The setpoint temperature may be provided as HotWaterTemperature
; if not provided, 125°F is assumed.
Depending on the type of water heater specified, additional elements are required/available:
WaterHeaterType | UniformEnergyFactor or EnergyFactor | FuelType | TankVolume | HeatingCapacity | RecoveryEfficiency | UsesDesuperheater | WaterHeaterInsulation/Jacket/JacketRValue | RelatedHVACSystem |
---|---|---|---|---|---|---|---|---|
storage water heater | required | <any> | <optional> | <optional> | <optional> | <optional> | <optional> | required if uses desuperheater |
instantaneous water heater | required | <any> | <optional> | required if uses desuperheater | ||||
heat pump water heater | required | electricity | required | <optional> | <optional> | required if uses desuperheater | ||
space-heating boiler with storage tank | required | <optional> | required | |||||
space-heating boiler with tankless coil | required |
For storage water heaters, the tank volume in gallons, heating capacity in Btuh, and recovery efficiency can be optionally provided. If not provided, default values for the tank volume and heating capacity will be assumed based on Table 8 in the 2014 Building America House Simulation Protocols and a default recovery efficiency will be assumed depending on the fuel type, as shown in the table below. The equations for non-electric storage water heaters are based on the regression analysis of AHRI certified water heaters.
FuelType | RecoveryEfficiency |
---|---|
Electric | 0.98 |
Non-electric, EF >= 0.75 |
\[0.778114 \cdot EF + 0.276679\]
|
Non-electric, EF < 0.75 |
\[0.252117 \cdot EF + 0.607997\]
|
For tankless water heaters, an annual energy derate due to cycling inefficiencies can be provided. If not provided, a value of 0.08 (8%) will be assumed.
For combi boiler systems, the RelatedHVACSystem
must point to a HeatingSystem
of type “Boiler”.
For combi boiler systems with a storage tank, the storage tank losses (deg-F/hr) can be entered as StandbyLoss
; if not provided, a default value based on the AHRI Directory of Certified Product Performance will be calculated.
For water heaters that are connected to a desuperheater, the RelatedHVACSystem
must either point to a HeatPump
or a CoolingSystem
.
Hot Water Distribution¶
A Systems/WaterHeating/HotWaterDistribution
must be provided if any water heating systems are specified.
Inputs including SystemType
and PipeInsulation/PipeRValue
must be provided.
For a SystemType/Standard
(non-recirculating) system, the following element are used:
PipingLength
: Optional. Measured length of hot water piping from the hot water heater to the farthest hot water fixture, measured longitudinally from plans, assuming the hot water piping does not run diagonally, plus 10 feet of piping for each floor level, plus 5 feet of piping for unconditioned basements (if any) If not provided, a defaultPipingLength
will be calculated using the following equation from ANSI/RESNET/ICC 301-2019.\[PipeL = 2.0 \cdot (\frac{CFA}{NCfl})^{0.5} + 10.0 \cdot NCfl + 5.0 \cdot bsmnt\]Where, PipeL = piping length [ft], CFA = conditioned floor area [ft²], NCfl = number of conditioned floor levels number of conditioned floor levels in the residence including conditioned basements, bsmnt = presence = 1.0 or absence = 0.0 of an unconditioned basement in the residence.
For a SystemType/Recirculation
system, the following elements are used:
ControlType
RecirculationPipingLoopLength
: Optional. If not provided, the default value will be calculated by using the equation shown in the table below. Measured recirculation loop length including both supply and return sides, measured longitudinally from plans, assuming the hot water piping does not run diagonally, plus 20 feet of piping for each floor level greater than one plus 10 feet of piping for unconditioned basements.BranchPipingLoopLength
: Optional. If not provided, the default value will be assumed as shown in the table below. Measured length of the branch hot water piping from the recirculation loop to the farthest hot water fixture from the recirculation loop, measured longitudinally from plans, assuming the branch hot water piping does not run diagonally.PumpPower
: Optional. If not provided, the default value will be assumed as shown in the table below.Element Name Default Value RecirculationPipingLoopLength [ft] \[2.0 \cdot (2.0 \cdot (\frac{CFA}{NCfl})^{0.5} + 10.0 \cdot NCfl + 5.0 \cdot bsmnt) - 20.0\]BranchPipingLoopLength [ft] 10 Pump Power [W] 50
In addition, a HotWaterDistribution/DrainWaterHeatRecovery
(DWHR) may be specified.
The DWHR system is defined by:
FacilitiesConnected
: ‘one’ if there are multiple showers and only one of them is connected to a DWHR; ‘all’ if there is one shower and it’s connected to a DWHR or there are two or more showers connected to a DWHREqualFlow
: ‘true’ if the DWHR supplies pre-heated water to both the fixture cold water piping and the hot water heater potable supply pipingEfficiency
: As rated and labeled in accordance with CSA 55.1
Water Fixtures¶
Water fixtures should be entered as Systems/WaterHeating/WaterFixture
elements.
Each fixture must have WaterFixtureType
and LowFlow
elements provided.
Fixtures should be specified as low flow if they are <= 2.0 gpm.
A WaterHeating/extension/WaterFixturesUsageMultiplier
can also be optionally provided that scales hot water usage; if not provided, it is assumed to be 1.0.
Solar Thermal¶
A solar hot water system can be entered as a Systems/SolarThermal/SolarThermalSystem
.
The SystemType
element must be ‘hot water’.
Solar hot water systems can be described with either simple or detailed inputs.
If using simple inputs, the following elements are used:
SolarFraction
: Portion of total conventional hot water heating load (delivered energy and tank standby losses). Can be obtained from Directory of SRCC OG-300 Solar Water Heating System Ratings or NREL’s System Advisor Model or equivalent.ConnectedTo
: Optional. If not specified, applies to all water heaters in the building. If specified, must point to aWaterHeatingSystem
.
If using detailed inputs, the following elements are used:
CollectorArea
: in units of ft²CollectorLoopType
: ‘liquid indirect’ or ‘liquid direct’ or ‘passive thermosyphon’CollectorType
: ‘single glazing black’ or ‘double glazing black’ or ‘evacuated tube’ or ‘integrated collector storage’CollectorAzimuth
CollectorTilt
CollectorRatedOpticalEfficiency
: FRTA (y-intercept); see Directory of SRCC OG-100 Certified Solar Collector RatingsCollectorRatedThermalLosses
: FRUL (slope, in units of Btu/hr-ft²-R); see Directory of SRCC OG-100 Certified Solar Collector RatingsStorageVolume
: Optional. If not provided, the default value in gallons will be calculated using the following equation\[StorageVolume = 1.5 \cdot CollectorArea\]ConnectedTo
: Must point to aWaterHeatingSystem
. The connected water heater cannot be of type space-heating boiler or attached to a desuperheater.
Photovoltaics¶
Each solar electric (photovoltaic) system should be entered as a Systems/Photovoltaics/PVSystem
.
The following elements, some adopted from the PVWatts model, are required for each PV system:
Location
: ‘ground’ or ‘roof’ mountedModuleType
: ‘standard’, ‘premium’, or ‘thin film’Tracking
: ‘fixed’ or ‘1-axis’ or ‘1-axis backtracked’ or ‘2-axis’ArrayAzimuth
ArrayTilt
MaxPowerOutput
Inputs including InverterEfficiency
, SystemLossesFraction
, and YearModulesManufactured
can be optionally entered.
If InverterEfficiency
is not provided, the default value of 0.96 is assumed.
SystemLossesFraction
includes the effects of soiling, shading, snow, mismatch, wiring, degradation, etc.
If neither SystemLossesFraction
or YearModulesManufactured
are provided, a default value of 0.14 will be used.
If SystemLossesFraction
is not provided but YearModulesManufactured
is provided, SystemLossesFraction
will be calculated using the following equation.
Appliances¶
This section describes elements specified in HPXML’s Appliances
.
Clothes Washer¶
An Appliances/ClothesWasher
element can be specified; if not provided, a clothes washer will not be modeled.
The Location
can be optionally provided; if not provided, it is assumed to be in the living space.
Several EnergyGuide label inputs describing the efficiency of the appliance can be provided. If the complete set of efficiency inputs is not provided, the following default values representing a standard clothes washer from 2006 will be used.
Element Name | Default Value |
---|---|
IntegratedModifiedEnergyFactor [ft³/kWh-cyc] | 1.0 |
RatedAnnualkWh [kWh/yr] | 400 |
LabelElectricRate [$/kWh] | 0.12 |
LabelGasRate [$/therm] | 1.09 |
LabelAnnualGasCost [$] | 27.0 |
Capacity [ft³] | 3.0 |
LabelUsage [cyc/week] | 6 |
If ModifiedEnergyFactor
is provided instead of IntegratedModifiedEnergyFactor
, it will be converted using the following equation based on the Interpretation on ANSI/RESNET 301-2014 Clothes Washer IMEF.
An extension/UsageMultiplier
can also be optionally provided that scales energy and hot water usage; if not provided, it is assumed to be 1.0.
Clothes Dryer¶
An Appliances/ClothesDryer
element can be specified; if not provided, a clothes dryer will not be modeled.
The dryer’s FuelType
must be provided.
The Location
can be optionally provided; if not provided, it is assumed to be in the living space.
Several EnergyGuide label inputs describing the efficiency of the appliance can be provided. If the complete set of efficiency inputs is not provided, the following default values representing a standard clothes dryer from 2006 will be used.
Element Name | Default Value |
---|---|
CombinedEnergyFactor [lb/kWh] | 3.01 |
ControlType | timer |
If EnergyFactor
is provided instead of CombinedEnergyFactor
, it will be converted into CombinedEnergyFactor
using the following equation based on the Interpretation on ANSI/RESNET/ICC 301-2014 Clothes Dryer CEF.
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
Dishwasher¶
An Appliances/Dishwasher
element can be specified; if not provided, a dishwasher will not be modeled.
The dishwasher is assumed to be in the living space.
Several EnergyGuide label inputs describing the efficiency of the appliance can be provided. If the complete set of efficiency inputs is not provided, the following default values representing a standard dishwasher from 2006 will be used.
Element Name | Default Value |
---|---|
RatedAnnualkWh [kwh/yr] | 467 |
LabelElectricRate [$/kWh] | 0.12 |
LabelGasRate [$/therm] | 1.09 |
LabelAnnualGasCost [$] | 33.12 |
PlaceSettingCapacity [#] | 12 |
LabelUsage [cyc/week] | 4 |
If EnergyFactor
is provided instead of RatedAnnualkWh
, it will be converted into RatedAnnualkWh
using the following equation based on ANSI/RESNET/ICC 301-2014.
An extension/UsageMultiplier
can also be optionally provided that scales energy and hot water usage; if not provided, it is assumed to be 1.0.
Refrigerator¶
An Appliances/Refrigerator
element can be specified; if not provided, a refrigerator will not be modeled.
The Location
can be optionally provided; if not provided, it is assumed to be in the living space.
The efficiency of the refrigerator can be optionally entered as RatedAnnualkWh
or extension/AdjustedAnnualkWh
.
If neither are provided, RatedAnnualkWh
will be defaulted to represent a standard refrigerator from 2006 using the following equation based on ANSI/RESNET/ICC 301-2019.
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
Cooking Range/Oven¶
Appliances/CookingRange
and Appliances/Oven
elements can be specified; if not provided, a range/oven will not be modeled.
The FuelType
of the range must be provided.
The cooking range and oven is assumed to be in the living space.
Inputs including IsInduction
(for the cooking range) and IsConvection
(for the oven) can be optionally provided.
The following default values will be assumed unless a complete set of the optional variables is provided.
Element Name | Default Value |
---|---|
IsInduction | false |
IsConvection | false |
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
Dehumidifier¶
An Appliance/Dehumidifier
element can be specified; if not provided, a dehumidifier will not be modeled.
The Capacity
, DehumidistatSetpoint
(relative humidity as a fraction, 0-1), and FractionDehumidificationLoadServed
(0-1) must be provided.
The efficiency of the dehumidifier can either be entered as an IntegratedEnergyFactor
or EnergyFactor
.
Lighting¶
The building’s lighting is described by six Lighting/LightingGroup
elements, each of which is the combination of:
LightingGroup/ThirdPartyCertification
: ‘ERI Tier I’ (fluorescent) and ‘ERI Tier II’ (LEDs, outdoor lamps controlled by photocells, or indoor lamps controlled by motion sensor)LightingGroup/Location
: ‘interior’, ‘garage’, and ‘exterior’
The fraction of lamps of the given type in the given location are provided as the LightingGroup/FractionofUnitsInLocation
.
The fractions for a given location cannot sum to greater than 1.
If the fractions sum to less than 1, the remainder is assumed to be incandescent lighting.
Garage lighting values are ignored if the building has no garage.
To model a building without any lighting, all six Lighting/LightingGroup
elements must be excluded.
A Lighting/extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
Ceiling Fans¶
Each ceiling fan (or set of identical ceiling fans) should be entered as a Lighting/CeilingFan
.
The Airflow/Efficiency
(at medium speed) and Quantity
can be provided, otherwise the following default assumptions are used from ANSI/RESNET/ICC 301-2019.
Element Name | Default Value |
---|---|
Airflow/Efficiency [cfm/W] | 3000/42.6 |
Quantity [#] | NumberofBedrooms+1 |
In addition, a reduced cooling setpoint can be specified for summer months when ceiling fans are operating. See the Thermostat section for more information.
Plug Loads¶
Plug loads can be provided by entering MiscLoads/PlugLoad
elements; if not provided, plug loads will not be modeled.
Currently only plug loads specified with PlugLoadType='other'
and PlugLoadType='TV other'
are recognized.
The annual energy consumption (Load[Units='kWh/year']/Value
) can be provided, otherwise they will be calculated using the following equations from ANSI/RESNET/ICC 301-2019.
An extension/UsageMultiplier
can also be optionally provided that scales energy usage; if not provided, it is assumed to be 1.0.
Validating & Debugging Errors¶
When running HPXML files, errors may occur because:
- An HPXML file provided is invalid (either relative to the HPXML schema or the EnergyPlus Use Case).
- An unexpected EnergyPlus simulation error occurred.
If an error occurs, first look in the run.log for details. If there are no errors in that log file, then the error may be in the EnergyPlus simulation – see eplusout.err.
Contact us if you can’t figure out the cause of an error.
Sample Files¶
Dozens of sample HPXML files are included in the workflow/sample_files directory. The sample files help to illustrate how different building components are described in HPXML.
Each sample file generally makes one isolated change relative to the base HPXML (base.xml) building.
For example, the base-dhw-dwhr.xml file adds a DrainWaterHeatRecovery
element to the building.
You may find it useful to search through the files for certain HPXML elements or compare (diff) a sample file to the base.xml file.